Sound protection design for DACH/European construction: Schallschutz per DIN 4109 (airborne R'w, D_nT,w; impact L'n,w, L'nT,w), C/Ctr spectrum adaptation, level arithmetic (10/20·lg rules, energy summing), point/line distance laws, mass law (30,9·lg m'-22,2 family), double-leaf walls (28+18·lg reduced-mass rule), resonance frequency f0 design and spring quality s', front shells (Vorsatzschalen) with delta-R_w(f0), floating screeds (164-35·lg m' bare slab, delta-L_w = f(m',s')), flanking paths a…
Install
npx vskill@latest install felixkarevo/construction-skills/building-acousticsSKILL.md
Building Acoustics (Schallschutz + Raumakustik)
Simple-first gate (governs how this skill is applied). Default every choice here tothe simplest proven solution at the agreed standard tier — see the governing skillsimple-first-building(complexity ladder §1). Escalate to more demanding construction(innovative systems, one-off details, higher comfort tiers) only when the clientexplicitly asks for it, with cost/schedule impact stated; deviate below the usualstandard or the aarRdT only via the documented risk-acceptance machinery(simple-first-building§3) — public permission never cures the private default.
Agent-neutral construction-design skill. English working language, German normative terms in parentheses. Metric units only. Applies to DACH practice; other countries must re-map norm references.
0. How to use this skill
- You are drafting, checking or explaining acoustic design in a building project:
ratings of walls/floors/windows, requirement selection, flanking verification, room-acoustics sizing, outdoor noise assessment.
- Read §1 (reality check) and §2 (evidence tiers) before quoting any number.
- Every table/formula below carries a tier tag: [T2] normative, [T3] digested
catalogue excerpt, [T4] rule of thumb. Values flagged VERIFY were ambiguous in the source material — confirm against the current norm before putting them in a deliverable.
- Cross-referenced sibling skills in this library (defer detail to them):
building-physics-thermal-moisture (Glaser/U-values of the same build-ups), construction-detailing (junction execution: screed bands, separations, seals), structural-systems, concrete-detailing, masonry-construction, timber-steel-design (load-bearing context for wall/floor catalogues), openings-windows-doors (window/door product ratings, mounting), building-services-tga (plant rooms, ducts, pipe decoupling), building-regulations-permits (Bauvorlage, immission approvals, LBO/MBO context).
1. Reality check — what this skill is and is not
- This is a planning and verification aid, not the deliverable. The formal
sound-insulation proof (Schallschutznachweis) is an Engineer/Architekt deliverable, signed per state building-authority rules (Prüfingenieur für Schallschutz in several Länder for certain classes). Output of this skill must be re-stated in the project's own documentation with norm editions cited.
- Norm editions move. DIN 4109-1/-2:2018, DIN 4109-3x catalogue parts (2016),
DIN 4109-5:2020, VDI 4100:2012 (earlier edition withdrawn), DEGA 103:2018, DIN 18041:2016 — all flagged verify current issue in the source material. Never assume an edition year from this file is still on the bookshelf.
- Beiblatt/catalogue status. DIN 4109-31…-36 are calculation-data parts
(Rahmen, massiv, Holz/Leichtbau/Trockenbau, Vorsatzschalen, Fenster/Türen, gebäudetechnische Anlagen). Catalogue values are design values, not test certificates; for products outside the catalogues you need Prüfzeugnis or measured data (DIN 4109-4).
- Site measurement cannot be replaced by calculation. Computed R'w is a
prediction for a stated room geometry; the acceptance question in disputes is answered by in-situ measurement per DIN 4109-4 / ISO 16283, which the calculation neither guarantees nor forbids failing.
- Minimum is not comfortable. Building to DIN 4109-1 alone satisfies public
law; neighbours' complaints in the "normal comfort" band are then a civil-law risk of the builder if the contract implied more (see §2).
- Geometry-specific results. A flanking computation is valid only for the
room dimensions it was run with (S_s, joint lengths, V) — re-run per room type.
2. Evidentiary tiers
| Tier | Status | Content | Consequence of use | |
|---|---|---|---|---|
| T1 | Legal anchor | LBO/MBO requirement that buildings be arranged/erected so sound from foreseeable nuisances does not cause "unzumutbare Belästigungen"; this makes the allgemein anerkannten Regeln der Technik binding — for building acoustics that core is DIN 4109 | Public-law minimum; deviation downward = non-approvable; owner/buyer can additionally demand higher standard (contract) — building only DIN 4109-1 while market/contract expectation is VDI 4100 SSt II is a known civil-law exposure | |
| T2 | Normative texts | DIN 4109-1 (requirements), -2 (simplified calculation), -3 (catalogue data), -4 (measurement); DIN 4109-5 (abgestufter/erhöhter Schallschutz); VDI 4100 (Nachhall-/Komfort-Level SSt I/II/III, private law); DIN 18041 (room acoustics); TA Lärm, 16. BImSchV, 18. BImSchV, DIN 18005, DIN EN ISO 9613-2, DIN ISO 717-1/-2 | Quote with edition; values here are excerpts | |
| T3 | Digested catalogue excerpts | Representative rows of the DIN 4109-32/-33/-34/-35 tables, requirement excerpts, absorption catalogues, junction formulas | Usable for design iteration; final proof re-derived from the norm | |
| T4 | Rules of thumb | Mass-law shortcuts, thickness→dB ladders, "decouple the screed" heuristics | Pre-design only, ±3…5 dB; label as estimate in any written output |
Perception anchors used throughout (T2, ISO/DIN framing): ±1 dB barely perceptible, ±3 dB clearly perceptible, 10 dB ≈ double/half loudness. For services noise the digest notes +5 dB(A) ≈ perceived doubling below ~40 dB(A).
3. Metrics, spectra and level arithmetic
3.1 Hearing bands and quantities [T2]
- Hearing 16 Hz–20 kHz; building acoustics evaluation band 100–3150 Hz
(third-octaves), room acoustics 63–8000 Hz; speech up to ~8 kHz.
- Third-octave mid-frequencies: 100, 125, 160, 200, 250, 315, 400, 500, 630,
800, 1000, 1250, 1600, 2000, 2500, 3150 Hz (building-acoustics set).
- λ = c/f; c = 344 m/s (air 20 °C) → λ(1 kHz) = 0.34 m.
- L_p = 20·lg(p/p₀) dB, p₀ = 20 µPa (0 dB hearing threshold; ~120 dB pain).
- L_W = 10·lg(W/W₀) dB, W₀ = 1 pW. L_p = L_W at r = 0.28 m (full-sphere source).
- Transmission degree τ = transmitted/incident intensity (10⁻¹…10⁻⁸);
R = 10·lg(1/τ).
3.2 Room-related descriptors (DIN 4109 / ISO 717 / ISO 16283) [T2]
| Symbol | Name | Definition | Notes | |
|---|---|---|---|---|
| D | Pegeldifferenz | D = L₁ − L₂ | depends on receiving room | |
| D_n | normalized level difference | D_n = D + 10·lg(A/A₀) | A₀ = 10 m² (25 m² for teaching rooms) | |
| D_nT | standardized level difference | D_nT = D + 10·lg(T/T₀) | T₀ = 0.5 s; ISO 16283-1; T₀ ↔ A ≈ 0.32·V | |
| R_w | weighted sound reduction index | lab, direct path only | single number, ISO 717-1 | |
| R'w | Bauschalldämm-Maß (apparent) | in-situ, includes flanking | prime = field quantity | |
| L'_n | normalized impact level | L_n = L + 10·lg(A/A₀) | tapping machine ISO 16283-2 | |
| L'_nT | standardized impact level | L'_nT = L_i + 10·lg(T/T₀) | T₀ = 0.5 s | |
| L_n,eq,0,w | equivalent normalized impact, bare slab | direct path, no topping | mass-law entry (§7) | |
| ΔL_w | impact improvement of a floor build-up | ΔL_w = L'_n0 − L'_n1 | floating screed/covering credit | |
| K_ij | Stoßstellendämm-Maß (junction attenuation) | structure-borne transmission quality at a joint | higher = better (§8) | |
| C, C_tr | spectrum adaptation values | subtract from R_w for real spectra | §3.3 | |
| C_I | impact spectrum adaptation | reported L'_n,w + C_I | §7.5 |
Naming convention (T2): R = calculated, P = lab (Prüfstand), B = built; X'w forms with prime are in-situ/flanking-inclusive. VDI 4100 works in D_nT,w / L'_nT,w (room-based); DIN 4109 in R'w / L'n,w (component-based); conversions in §9 — keep them apart in tables or auditors will reject the mix.
3.3 Spectrum adaptation C / C_tr [T2]
- C (spectrum 1 — residential/announcement-like: speech, music, radio/TV,
children playing; also high-speed rail, motorway > 80 km/h, jets near, mid/high-frequency industry).
- C_tr (spectrum 2 — traffic-like: city traffic, low-speed rail, aircraft
distant, disco; low/mid-frequency industry).
- Weighted results: A_w,1 = X_w + C; A_w,2 = X_w + C_tr.
- Reporting style:
R'w(C; C_tr) = 53(−1; −4) dB— single number alone hides
low-frequency weakness; for traffic noise check Ctr, for mixed residential use C (Tafel guidance: Ctr for city traffic, C for dwelling pink noise).
- Typical digested values: homogeneous masonry single leaves C = −1.6,
C_tr = −4.6 dB; timber floors C_I positive, bare RC negative (−15 ≤ C_I ≤ 0).
3.4 ISO 717-1 reference curve (airborne rating) [T2]
Shift the reference curve in 1 dB steps toward the measured/calculated curve until Σ deficiencies over the 16 thirds ≤ 32 dB; R_w = curve value at 500 Hz. Reference curve (thirds 100→3150 Hz):
| f | 100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 800 | 1k | 1250 | 1600 | 2000 | 2500 | 3150 | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| R | 33 | 36 | 39 | 42 | 45 | 48 | 51 | 52 | 53 | 54 | 55 | 56 | 56 | 56 | 56 | 56 |
Octave shortcuts (125/250/500/1k/2k): 36/45/52/55/56. Worked shift example (§13 F6): data −9 shift → R'w = 52 − 9 = 43 dB with ΣU = 25 ≤ 32.
3.5 A-weighting (excerpt) [T2]
A-corrections, dB, by third: 100 −19.1 · 125 −16.1 · 160 −13.3 · 200 −10.9 · 250 −8.6 · 315 −6.6 · 400 −4.8 · 500 −3.2 · 630 −1.9 · 800 −0.8 · 1000 0 · 1250 +0.6 · 1600 +1.0 · 2000 +1.2 · 2500 +1.3 · 3150 +1.2. Modern instruments: A and C networks only.
3.6 Level arithmetic [T2]
- Addition (incoherent sources): L_tot = 10·lg Σⱼ 10^(0.1·Lⱼ).
- n equal sources: L_tot = L + 10·lg n (2× → +3 dB, 4× → +6 dB, 10× → +10 dB).
- Subtraction: L_x = 10·lg(10^(0.1·L_tot) − 10^(0.1·L_rest)).
- Leq over T: energy average; Leq = 10·lg[(1/T)∫10^(0.1L(t))dt].
- Worked: 54+58+50+49 → 60.0 dB (S1); 7 cars @ 84 → 84+10lg7 = 92.7 ≈ 92;
- plane 100 → 10lg(10^9.27 + 10^10) = 101 dB(A) (S2); from a total of 84 dB(A)
removing a 77 dB(A) residual: L₅ = 10lg(10^8.4 − 10^8.3) = 77 dB(A) (S3).
- Rule: subtracting a source ≥10 dB quieter than the sum changes nothing audibly;
−1 dB on a 94.6 dB orchestra means killing 12 of 25 blowers (S5).
3.7 Distance laws [T2]
- Point source, free field: ΔL = 20·lg(r₂/r₁); L_p = L_W − 11 − 20·lg r (m).
Reflecting planes: 1 plane −8, 2 planes −5, 3 planes −2 (instead of −11).
- Line source: ΔL = 10·lg(r₂/r₁) — doubling distance −3 dB only.
Free cylinder: L_p = L_W − 8 − 10·lg r; over ground (semi-cyl): −5 constant.
- Worked (S4): machine L_W = 101 dB(A), mixed-area day limit 60 dB(A), hemispherical
radiation: r = 10^((101−8−60)/20) = 44.7 m → place ≥ 45 m; at 20 m the admissible L_W,max = 60 + 8 + 20·lg 20 = 94 dB(A).
4. Mass law — single-leaf elements
4.1 Theory [T2/T4]
Theoretical mass law (ideal plate, zero bending stiffness): R(f) = 10·lg[1 + (2π·f·m′/(2·ρ·c))²]; → +6 dB per octave and +6 dB per mass doubling; dips at grazing incidence and at the coincidence (Koinzidenz) limit frequency f_g, where the acoustic trace wavelength matches the bending wavelength.
- f_g < 100 Hz → treat as "sufficiently stiff" (biegesteif);
- f_g > 1500–2000 Hz → "sufficiently flexible" (biegeweich) — flat mass-law run;
- f_g inside 200–2000 Hz → coincidence dip is design-relevant (gypsum board,
CLT, thin stone: check catalogue or measure).
- Old-form shortcut (non-normative, still circulating): R_w ≈ 20·lg(m′·f) − 47.5
at f = 500 Hz (T4, VERIFY against current data parts before use).
4.2 Normative one-leaf design formulas (DIN 4109-32) [T3]
For quasi-homogeneous masonry (conditions §4.3), surface mass m′ = d·ρ_eff (kg/m²), weighted direct rating R_w from lg m′:
| Material family | Formula (63…720/480 kg/m² validity) | |
|---|---|---|
| Concrete / KS / Vollziegel / filled blocks | R_w = 30,9·lg(m′) − 22,2 (65–720 kg/m²) | |
| Lightweight concrete masonry (LB) | R_w = 30,9·lg(m′) − 20,2 (140–480 kg/m²) | |
| AAC (Porenbeton) m′ < 150 | R_w = 32,6·lg(m′) − 22,5 | |
| AAC (Porenbeton) m′ ≥ 150 | R_w = 26,1·lg(m′) − 8,4 |
This is the start of the file. Read the full SKILL.md on GitHub.
Security
- Security scanPassed, 100 of 100Pattern checks on the skill's files.
- Model reviewNot runA model review is scheduled for the next rescan.
Quality evaluation
- Task evaluationNot runNo evaluation yet. Run one in Skill Studio.
Source
- SKILL.md in the repositoryCheckingskills/building-acoustics/SKILL.md
Popularity
- 7-day trend score
- 0
Not refreshed yet.
Works with
Any agent vskill installs to: 56 targets in all. These 39 have a page on this site.
- Claude Code
- Cursor
- GitHub Copilot
- Windsurf
- Codex
- Gemini CLI
- Cline
- Amp
- Roo Code
- Goose
- Continue
- Kilo Code
- Junie
- Trae
- OpenHands
- Qwen Code
- AI Agent
- Tabnine Chat
- Sourcegraph Cody
- Amazon Q
- Firebase Genkit
- Sweep
- Devin
- Phind
- Mentat
- Claude Desktop
- Aider
- GPT Pilot
- Plandex
- bolt.new
- v0
- Replit Agent
- Anse
- TypingMind
- BetterChatGPT
- LibreChat
- Warp AI
- Pieces
- Fig AI
Embed badge
[](https://verified-skill.com/skills/felixkarevo/construction-skills/building-acoustics)