name: building-planning-spatial description: > Turn a plot into a dimensionally defensible house plan in the German regulatory context (DACH): B-Plan / §34 BauGB read (Maß der Nutzung: GRZ, GFZ, OWZ, Bauweise, Zahl der Vollgeschosse, Wandhöhe; Baufenster; setbacks via Abstandsflächen der LBO — B-Plan-dependent figures marked VERIFY), envelope test (coverage vs. plot-ratio vs. setback bindingness), brief fitting at generic international room minimums (retagged, not German law) plus family-house / single / duplex / multifamily sizing heuristics, Neufert anthropometric body- dimension and movement-envelope tables backing furniture/circulation clearances, orientation and sun geometry (solar altitude h = 90 − φ ± 23.5°, shading formulas, winter/summer contrast, DACH latitude table Berlin/München/Hamburg/Frankfurt), circulation % and NTG targets, wet-zone stacking and structural-grid coordination (span rules tagged to conception digest), staircase-first and courtyard/light-well placement, privacy/noise adjacencies (sleeping-side quiet, cross-ref building-acoustics), room-to-room quality checks, one worked example on a generic 600 m² B-Plan site (GRZ 0.4 shown as explicit placeholder), compute-don't-eyeball plan verification checklist, FreeCAD/BIM handoff (site object, storeys via Arch.makeFloor — Elevation-vs-Placement.Base.z gotcha, IFC Site>Building>Storey hierarchy), and sibling routing (building-typology, structural-systems, stairs, accessibility, building-regulations-permits). metadata: version: "1.0.0"


Site and Spatial Planning for Houses (German / DACH Context)

Simple-first gate (governs how this skill is applied). Default every choice here to
the simplest proven solution at the agreed standard tier — see the governing skill
simple-first-building (complexity ladder §1). Escalate to more demanding construction
(innovative systems, one-off details, higher comfort tiers) only when the client
explicitly asks for it, with cost/schedule impact stated; deviate below the usual
standard or the aarRdT only via the documented risk-acceptance machinery
(simple-first-building §3) — public permission never cures the private default.

This skill turns a plot in the German planning system into a house plan whose every dimension can be defended: how big the buildable envelope really is under the Bebauungsplan (or §34 BauGB where none exists), whether the brief fits it, how large each room should be, how wide passages and stairs must be, where the staircase and any courtyard go, and which way the house faces for winter sun and summer shade. Every number carries an evidentiary tier (Section 0): the binding figures are per-parcel (the B-Plan); this document demonstrates the method with clearly-flagged placeholders.

Use it before modelling (handoff Section 14), alongside siblings: building-regulations-permits (authoritative regulatory read — B-Plan text, state LBO, Genehmigung procedure; this skill cannot stand alone there — Sections 0/9.5), structural-systems (spans/grids/load-bearing logic), building-typology (house form, unit configuration), stairs (design beyond 5's placement arithmetic), accessibility-universal-design (DIN 18040-2), building-acoustics + building-physics-thermal-moisture (noise adjacencies, summer-heat proof).


Reality Check — Licensing & Liability

This skill produces design aids and calculation guidance for planning and FreeCAD/BIM modelling ONLY. Nothing here is a construction document, a statical calculation, or an approvable planning drawing (genehmigungsfähiger Entwurf).

  • Bauvorlageberechtigung (who may sign in/submit Bauvorlagen) is **state

law** (LBO per Bundesland, MBO-derived: Entwurfsverfasser in the Architektenkammer, Tragwerksplaner for stability, limited procedures for small buildings in some states). The digested fundamentals source explicitly does NOT cover it — treat every licensing statement as VERIFY via building-regulations-permits.

  • A real building needs a Baugenehmigungsverfahren (or state exemption/

notification procedure — VERIFY) proving conformity with the B-Plan or §34/§35 BauGB, the LBO (Abstandsflächen, Rettungswege, Rauchmelder, Stellplätze) and GEG/DIN 4108. The B-Plan of THIS parcel overrides every GRZ/GFZ/setback number printed here — especially the VERIFY-flagged ones.

  • If a user treats output as final (Bauantrag, ordering precast, earthworks),

say so unprompted: "Planning study — binding figures come from the parcel's Bebauungsplan and the state LBO; a Bauvorlageberechtigter signs and the authority approves before anyone builds."

  • Out of scope here: structural design (structural-systems,

structural-analysis), seismic (mostly Erdbebenzone 0 per DIN EN 1998-1/NA, non-zero at Oberrheingraben + Alpine fringe — VERIFY map; seismic-design), ground (geotechnics-foundations), fire (fire-protection-building), services. Plan-configuration regularity (2.6) stays here — plan shape is decided here.


Section 0: Evidentiary Tiers — Which Numbers Are Law

German residential building law does not codify minimum bedroom areas, kitchen sizes or corridor widths. Binding are (a) the land-use plan for this exact parcel (B-Plan, else §34 context) and (b) the state building code (Abstandsflächen, egress, smoke alarms…). Room sizes are market norms or, for subsidised/rental stock, programme definitions. State the tier when quoting.

TierLabelSourceStatusUse for
T1Legally binding for THIS parcelBebauungsplan (text + plan), örtliche Bauvorschriften, Erschließungsvertrag; state LBOEnforceable; approval fails against itGRZ, GFZ, OWZ, Bauweise, Zahl der Vollgeschosse, Wandhöhe, Baufenster, setbacks, Stellplatzsatzung
T1-VLegally binding in kind, but UNVERIFIED placeholder in this fileSame category, but this document could not check the figure against a specific B-Plan/LBO textPlanning placeholder only. Confirm from the parcel's own B-Plan extract / state LBO before anything beyond first-pass massingEverything in Sections 1.6, 2, 5.1 that carries a VERIFY tag
T2Codified technical rules (DIN / Eurocode / MBO §-level)MBO §§ (Abstandsflächen, Treppen §35), DIN 4108, DIN 4109, DIN 18040, DIN 1986Law by reference (Verwaltungsvorschrift) or recognised rules of technology — but state adoption varies; digest sources cover only partsStair step bands, minimum thermal R-values, sound classes, drainage gradients — VERIFY per state/standard edition
T3International reference floorGeneric habitable-room minimums (7.5/9.5 m² lineage), openable-window 1/10 practice (German pattern: rough window opening ≥ 1/8 of the floor area, MBO § 47, S.1)Not German law. Sanity floor onlyProving a tight room is not absurd; daylight/vent sanity checks
T4Built practice / market normGerman housing market: Neufert-derived furniture clearances, common EFH/DHH/MFH sizesNo legal force; reflects buyer/tenant expectationAll room sizes you quote clients; unit-mix sizing
T5Physics / study-backedSolar geometry (exact), thermal/moisture researchGeometry is certain; performance numbers are study-specificSun altitudes, overhang math, courtyard daylight, overheating logic

Hard rules:

  1. Never present a T3/T4 room-size number as German law. Say: *"7.5 m² is a

generic international floor, not a German requirement; the market builds 12–16 m² bedrooms and buyers expect that."*

  1. **Never present a T1-V figure (any GRZ/GFZ/setback in this file) as if it

had the standing of the parcel's actual B-Plan.** Say "B-Plan-dependent — typical range, VERIFY" every single time you quote one.

  1. Design to T4; test against T1/T1-V; cite T2/T3 only as a floor. German

market reality: a plan built to reference minimums reads as a social-housing unit, not a family home, and will resell badly even if it is "compliant."

What the digested fundamentals do and do not cover (so you know where this file stands alone): the source handbook digested for this library covers the technical basic disciplines (surveying, building physics, construction chemistry, construction IT/CAD/BIM, structural mechanics, reliability) and explicitly does not contain the Bauleitplanung procedure, Bauvorlageberechtigung, HOAI phase logic, or the permitting process. Where Section 1.1 sketches the FNP → B-Plan chain, it is common-knowledge framework for orientation — VERIFY the procedure and every §-citation against `building-regulations-permits`.


Section 0.5: The Working Sequence

In order. Skipping steps 1–2 wastes every later decision: the envelope determines the brief, never the reverse.

1. READ THE PLAN B-Plan? get text + key plan; else §34 (1.7). Extract Art
der Nutzung, GRZ, GFZ, OWZ/Vollgeschosse, Wandhöhe,
Bauweise, Baufenster, setbacks. Anything not read from
the parcel's own plan = VERIFY placeholder, said aloud. → §1
2. FIX THE ENVELOPE footprint vs GRZ vs Baufenster vs Abstandsflächen; floors
vs GFZ; height vs clause. Adopt the most restrictive. → §2
3. TEST THE BRIEF rooms at T4 sizes vs available NRF. If it doesn't fit,
resolve NOW, not in plan. → 3.8
4. FIX ORIENTATION φ → sun altitudes; street/noise side; shading geometry.
Free now, impossible later. → §6–7
5. PICK THE ARCHETYPE Bauweise + frontage + brief + depth. → 8.8 tree
6. PLACE THE STAIR before any room; compute risers from the real F2F. → §5
7. PLACE COURT/WELL W/H vs winter sun altitude at THIS φ; roof/floor cut =
diaphragm item (2.6). Tight row → Lichtschacht, honestly
named. → §6
8. LAY OUT ROOMS T4 sizes, wet stacks, quiet-to-quiet, buffers to street/
north. → §3, 9, 11
9. VERIFY GRZ/GFZ/height/setbacks/circ%/NTG/openable/W-H/regularity.
Compute; do not eyeball. → §10, 12, 13
10. STATE THE CAVEAT study status + named unverified placeholders + per-decision
2.6 flags, attached to the decisions, not as boilerplate.

Rule: never reach step 5 with step 1 unresolved — "assume GRZ 0.4" is how plans die after they are drawn.


Section 1: The German Planning Read — FNP, B-Plan, §34

1.1 The Bauleitplanung chain (framework — VERIFY procedure against building-regulations-permits)

Two-tier statutory land-use planning (BauGB):

Flächennutzungsplan (FNP) preparatory land-use plan, municipality-wide,
│ not binding on the citizen — binds the
↓ administration
Bebauungsplan (B-Plan, Bebauungsplan der Innenentwicklung §13a /
│ Regel-Plan §12) qualified urban development plan: legally
↓ binding for every parcel it covers
Bauvorlage + Baugenehmigung the individual building permit checks the
project against the B-Plan (§30 BauGB:
"zulässig", wenn nicht die Festsetzungen
widersprochen wird)
  • Inside a B-Plan → §30 BauGB: every Festsetzung governs: use type, measure

(GRZ/GFZ/OWZ), Bauweise, Vollgeschosse/Wandhöhe, überbaubare Fläche (Baufenster/Baugrenze), street setback — sometimes roof form, wall caps, planting duties.

  • **No B-Plan, parcel inside a zusammenhängende Bebauung → §34 BauGB

("im Innenbereich"): the project is to be approved if it *fits the surrounding character* (Eigenart der näheren Umgebung) in use-type, measure and construction method and Erschließung is secured. §34 has no numbers** — you derive the envelope by measuring what is built around you (1.7).

  • Außenbereich → §35 BauGB: building outside settled areas is in principle

not permitted (privileged uses excepted). If a user's plot is Außenbereich, stop and route to building-regulations-permits — spatial design is moot.

1.2 Art der baulichen Nutzung — what the plan lets you build

BauNVO area types you will meet on residential plots (the B-Plan states one; VERIFY per plan):

CodeTypeWhat it allows
WAAllgemeines WohngebietDwelling-dominated; small businesses run by residents tolerated
WRReihenhausgebietRow houses only — single/duplex row typology forced
WAllgemeines Wohngebiet (old plans) / Kleinsiedlungsgebiet KSSmall-lot housing; often tighter GRZ
MMischgebietLiving + non-disturbing trade — noise exposure from the trade side, see 7.6
MD/MIHochhaus-/Urbanisierungsbereiche, SondergebieteDense/urban variants — special rules, pull the plan
SSondergebietPurpose-specific (e.g. "Wohnen und Gastronomie") — read the text, nothing standard applies

Consequence: WR = row segment; WA+offen = single or duplex ("Einzel- und Doppelhäuser" — plan text); WA+geschlossen = row segment even on wide plots. Section 8's tree starts from Bauweise, not taste.

1.3 Maß der baulichen Nutzung I — GRZ (Grundflächenzahl)

GRZ = buildable ground area ÷ plot area (§17 BauNVO; the measure includes all covered ground surfaces — see the trap below).

  • B-Plan-dependent, typical WA/WR range roughly 0.2 – 0.6 (common row-house

plans 0.25–0.4; dense urban quarters up to ~0.6). VERIFY — these are ranges remembered from typical plans, not from the digested sources, which contain no GRZ values at all.

  • What counts (the trap): footprint + garages/Carports + Stellplätze +

Zufahrten + befestigte Wege + terraces (plan wording) + Aufschüttungen — the B-Plan text defines the list and may grant half-credit ("Minderanrechnung" — VERIFY). A 150 m² house on 600 m² is GRZ 0.25 until drive + carport push 0.38. Tally the whole plot's paved surfaces, not just the house.

1.4 Maß der baulichen Nutzung II — GFZ and OWZ

GFZ = total gross floor area of all storeys ÷ plot area (§19 BauNVO, measured to the outer face of the enclosing walls, per storey, in principle above ground).

  • B-Plan-dependent; typical residential range roughly 0.2 – 1.2

(EFH/EFH-Reihen plans commonly 0.25–0.6; row-house plans ~0.4–0.8; dense blocks higher). VERIFY — no GFZ value exists in the digested sources; every number here is a placeholder for demonstration.

  • **What counts (rule-of-thumb — the local calculation ordinance governs,

VERIFY): fully-served storeys count; the Keller usually does not if it lies below the terrain line it is measured from (a walk-out basement on sloping ground can count on its daylit face — the single most common §34-argument in German practice); Dachgeschoss/Renaissance counts where rooms are habitable-served, plan-text dependent; balconies/loggias commonly only a fraction (e.g. half) in modern plans — always the plan text.**

  • **OWZ (Obergeschosszahl / Zahl der baulichen Anlagen — some plans) vs "Zahl

der Vollgeschosse":** the plan expresses height either as a fixed number of full storeys (with eaves height limits, often "2-Vollgeschosse, Wandhöhe 7,00 m" style — placeholders) or as a maximum wall height. A Vollgeschoss is classically a storey whose ceiling is ≥ half above the adjoining terrain (plan-text definitions vary — VERIFY).

1.5 Height and roof: Wandhöhe, Vollgeschosse, Dachform

  • Wandhöhe: height of the exterior wall up to the eaves/roof edge, measured

from the determined terrain (often "Mittelgelände" or the street-side sidewalk line — the plan states its own measure line; VERIFY; this decides whether a "2½-storey-looking" house is 2 or 3 full storeys on paper).

  • Dachform/Dachneigung: many WA/WR plans fix flat / dual-pitch / hip and a

pitch band (e.g. 22°–38° — plan-dependent). This forces roof volume and usable DG area; some newer plans additionally set a PV clause or Solarpflicht (state law) — VERIFY plan graphics before shaping the roof.

  • If the plan says nothing on roof: fit the neighbours under §34.

1.6 Where you may stand: Baufenster, Bauweise, Abstandsflächen

Three independent controls that each can bind — run all three, adopt the smallest buildable rectangle:

  1. Baufenster / überbaubare Fläche (B-Plan). The plan draws a buildable

window: front distance from the street boundary (commonly ~5–10 m — placeholder), lateral reach, sometimes depth. Outside the Baufenster you may not build except minor exemptions the plan text lists (porches, single- storey annexes ≤ x m² — VERIFY per plan).

  1. Bauweise (BauNVO §16). offen: single/double houses, touching only at

short sides; geschlossen: segments built together at the front line. The classical offen side-gap (3.0 m/side ⇒ 6 m between houses) is older-rule/ plan-dependent, VERIFY — and usually superseded by (3).

  1. Abstandsflächen (state LBO, from MBO §6). Even inside the Baufenster you

must keep a setback from each boundary: the common formula family is A ≥ 3.00 m and A ≥ 0.4 × H (H = wall/storey height relevant per state definition — some states 0.4H to eaves/roof top, some count only storeys; state law, VERIFY; digested sources do NOT contain the formula — only the concept that these legal distances must hold in setting-out). A reduced or zero setback needs the neighbour's documented Abstandsflächenerklärung / Grenzerleichterung (BauNN). Boundary walls/garages: many states allow low ancillary structures directly on the boundary up to a length/height cap (e.g. ~3 m wall, ~9 m length, ~3 m height — classic MBO-derived figures, VERIFY in your state).

Setback-vs-coverage interaction (universal logic, kept): On a 24×25 m plot with 3 m side setbacks, setback-buildable width is 18 m; a GRZ 0.4 cap of 240 m² may bind instead (18 × 13.4 = 240). Always run all three and adopt the smaller footprint; always re-confirm which of them binds in the plan text.

1.7 §34 fallback — deriving the envelope without a plan

No B-Plan (typical for Baulücken in old quarters, village insets, outer suburban streets): you must document the Umgebungsanalyse:

1. Map the 3–5 nearest comparable parcels (same side, similar width): build
depth off street, storeys, eaves height, footprint/plot ratio, Bauweise, roof.
2. Form the range (e.g. neighbours 6.5–9 m off street, 2+ADG, eaves 6.8–7.4,
footprint 0.28–0.42 of plot).
3. Sit inside the range; the middle is the defensible claim, extremes invite
objections. 4. Write the derivation down BEFORE designing — the Bauamt
asks (Bauvorlagen → building-regulations-permits).

Numbers from this method are survey facts (measured), not law — they are as citable as a §34 opinion can be. VERIFY with the authority in a Bauvorbescheid (pre-decision, §72-BauGB-analog state provision — VERIFY) when the envelope is tight. A Bauvorbescheid before designing a full plan is the German equivalent of "ask first" — recommend it whenever §34 ranges are wide.

1.8 Plot geometry — metric, and frontage is still the binding constraint

German plots are metric — but the frontage trap is universal and sharper in Baugebiete, because parcels of identical area differ wildly in shape (300 m² at 10 × 30 m vs 17 × 18 m are different buildings).

Frontage (B-Plan row plots)What fits across the width (after 3 m setbacks or party walls)Plan structure forced
5.5–7 m (WR row segment)one 3.5–4.5 m room bay + 1.25 m circulation/coreRow segment: rooms front/back, stair along one side
8–10 m (DHH half-plot, one side built to boundary)5.5 m room + 1.0 m stair on shared line, or 2 baysDuplex: stair on party side, garden axis to the open side
12–15 m (offene Bauweise EFH)6 m living + 1 m gap + 5.5 m room, or room+Flur+roomFreistehend: full room-to-room plans possible
16–20 m (large EFH / small MFH)3 bays: 5.5 + core 1.5 + 5.5 + ...MFH starting point: 2 units per floor back-to-back

Deduct: two 24–36.5 cm external walls ≈ 0.5–0.7 m gross-to-clear across the width (wall thickness Section 9.3), plus ~12 cm per crossed internal wall. When a client can choose a 15 × 40 m parcel or a 20 × 30 m parcel of equal area, the wider one is materially more plannable — frontage, not area, binds the section of the plan.

1.9 Orientation nomenclature

Parcels are described by street/garden side: "Südgarten" (garden south) is the market premium; north street + south garden is ideal and common in rows. Street side = entrance + noise side (7.6); garden side = winter-gain facade. West- garden plots need the shading + buffer strategy from day one (7.2–7.4).


Section 2: The Envelope Test — GRZ, GFZ, Height, Setbacks

2.1 Placeholder schedule for the worked example (T1-V — NOT a real plan)

The generic 600 m² site used in Sections 2.2 and 12.5 assumes:

Bebauungsplan (hypothetical, method demonstration ONLY):
Nutzung WA, offene Bauweise (Einzel- + Doppelhäuser)
GRZ 0.4 · GFZ 0.8 · VGS 2 (+ ausgebautes DG? — placeholders, VERIFY)
Wandhöhe bis 7,10 m (placeholder); Baufenster ab Straße 8 m, hinten ≥ 3 m
Side setbacks per LBO: A = max(3.0 m, 0.4·H) — formula family, VERIFY
2 Stellplätze/WE; garages/Carports count (full or half) against GRZ per
plan text — VERIFY.

Replace every line with the parcel's actual plan before the study leaves the drafting table — the arithmetic below is the product; the numbers are props.

2.2 What the placeholders permit — the arithmetic, method-valid regardless

600 m² site, GRZ 0.4 / GFZ 0.8, 2 full storeys (+optional DG):

QuantityCalcResult
Max ground area (whole-plot, incl. paving!)600 × 0.4240 m²
House footprint if driveway+carport eat 60 m²240 − 60180 m² house
Max gross above-ground floors (GFZ)600 × 0.8480 m²
→ floors at full 240 plate480 / 2402.0 → exactly 2 storeys
→ floors at 180 plate (realistic)480 / 1802.7 → 2 floors + DG ~100 m²
Keller (walk-in, under house, plan-exempt — VERIFY)excluded from GFZ per placeholder reading−

Reading it (method holds for any confirmed figures): GRZ binds the ground (every paved m²); GFZ binds total floors; the height clause binds the storey number; the Keller lever (if plan-exempt AND buildable, 2.4) is the German version of "the biggest lever on a tight plot".

Massing decision tree:

Client wants N m² gross above-ground on plot A with (GRZ, GFZ):
├─ N ≤ A×GRZ_eff → single storey; garden maximised; done.
├─ N ≤ 2×plate & ≤ A×GFZ → 1.5–2 storeys at full plate.
├─ N ≤ A×GFZ, > 2×plate → 2 storeys + DG — DG counts GFZ only if the plan
│ says so: VERIFY before banking it.
└─ N > A×GFZ → not permissible as drawn: (a) cut brief (3.8),
(b) Keller if plan-exempt + soil OK, (c) larger
plot/zone, (d) §34 measured-surroundings argument
or Bauvorbescheid before designing more.

2.3 Setback check worked on the placeholders

House 18.0 × 10.0 m, Wandhöhe (eaves, flat roof) 6.30 m, plot 24 wide × 25 deep:

Side: A = max(3.00, 0.4×6.30 = 2.52) → 3.00 m per side (formula family VERIFY)
buildable width 18.00 ≥ 10.00 house width ✓
Front: Baufenster at 8.0 m street setback → rear gap 25 − 8 − 10 = 7.0 ≥ 3 ✓
GRZ: house 100 + drive 40 + paths/carport 35 = 175 ≤ 240 ✓
VERDICT: here the Baufenster binds position and GRZ the paving budget; on
narrower plots the setbacks bind. RUN ALL THREE; state which binds.

2.4 Basement caveats (German)

  • GFZ/GRZ treatment of the Keller is plan-text law: recurring clause

families cap the exposed basement wall height above mean terrain (≈ 1.0 m class) or count daylit faces — VERIFY the wording.

  • Physical: water table/flooding (Hochwassergefahrenkarten — state maps; since

2021 "HQ-extrem" is a standard question; geotechnics-foundations): legal and buildable are different tests; run both before recommending the Keller lever.

  • Cost is volatile — never quote a Keller price from memory; but relative

logic holds: a GFZ-exempt Keller often buys more legal area than the next plot band.

2.5 Non-negotiable open space, whatever the plan allows

Even at GRZ 0.6 legal ceilings, reserve:

  • Rear open depth ≥ 3 m behind south-glazed living: without it the terrace

is a light-well and the winter-gain facade gains nothing.

  • One buildable-free strip to a boundary unless the plan's Abstandsflächen

are formally waived — neighbours later build to the line; windows at 3 m face windows (privacy: Section 7.6).

  • Stellplätze + manoeuvring (3.7) with GRZ accounting of ALL paved m².
  • Haustechnik-Zugang: tank/plant access, rainwater cistern (many plans

require retention — Rückhaltung nach Entwässerungssatzung, VERIFY), Kelleraußentreppe egress.

2.6 Plan-configuration risk — what THIS skill controls

Full seismic design is seismic-design's and the Tragwerksplaner's (Germany: mostly DIN EN 1998-1/NA zone 0; Oberrheingraben + Alpine fringe non-zero — VERIFY the map for the site). But German practice regularity issues that get decided HERE and cannot be undone later are the same physics everywhere:

Plan decision made hereRisk if carelessMitigation at planning stage
L-shape / re-entrant cornertorsional concentration at the inner corner (seismic AND differential-settlement AND rendering-crack classic)wings ≤ 1:3 aspect; movement joint or slip joint at the re-entrant; tell structural-systems explicitly
Courtyard / Atrium cutdiaphragm hole: floor load redistribution around the voidcentre the cut; edge beams all four sides; flag as design intent, not detail afterthought
Long single-bay wing (Galerie, "Haus am Hang")soft/weak axis, big eccentricitieskeep width:length ≤ ~1:4; intermediate cross walls per structural-systems
Split levels on slopediscontinuous shear path at every offseton zones 0: usually acceptable, watch crack control; on 1–2: prefer terraced full floors — route to seismic-design
Columns stranded off gridirregular load path, cost9.4 rule 1

Handoff rule: whenever Section 8's tree lands on an L, a court, a long wing or a split level, write the specific note into the model handoff — "re-entrant corner at grid C/4 — check for seismic zone per national annex + settlement joint", not a generic disclaimer.


Section 3: Room Program — Generic Minimums vs What the German Market Builds

3.1 Generic international reference minimums (T3 — NOT German law, VERIFY never needed because nothing here binds)

German public building law sets no minimum room sizes for owner-occupied houses. The table below is the generic international habitable-room lineage (metric restatement) — keep it only as a sanity floor:

SpaceGeneric floorNote
Habitable room, single-room dwelling9.5 m²absolute floor
Other habitable rooms (bed, living, dining)7.5 m²≈ 2.7×2.8 m
Kitchen, separate5.0 m²
Bathroom (bath only)1.8 m²
WC only1.1 m²
Combined bath + WC2.8 m²≈ 1.5×1.9 m
Window openable sanity≥ 1/10 of floor areapractice rule, not DIN
Window size, German patternrough opening ≥ 1/8 of the net floor areaMBO § 47, read again in three books (S.1); some states accept 1/10. Governs where the two differ
Ceiling height2.50 mstate LBOs commonly require "angemessene Höhe"; many fix ≥ 2.40–2.50 m for Wohnräume — T2, state-specific, VERIFY. MBO: at least 2.40 m clear (S.1)

German-law adjacents you must not confuse with these: DIN 18040-2 (barrier-free — binding only if claimed/subsidised), state Wohnraum definitions and the Zweckentfremdungs-/Ortspolizeirecht of tight housing markets (a too-small or windowless room may not count as a lettable bedroom — city- specific, VERIFY). None of them make 7.5 m² a marketable bedroom anywhere in DACH practice — see 3.2.

3.2 German built-practice targets (T4) — design to these

Interior clear, single/duplex house (EFH/DHH/Reihenmittelhaus), typical new-build band (market convention — no legal force; verify against the buyer's expectations and the resale norm):

SpaceCompact (row/DHH)Comfortable (freistehend)Generous
Wohnen (living)22–2628–3640–55
Essen (dining, incl. open to kitchen)within Wohnen12–1616–20
Kochen (kitchen)7–910–1414–20 (Wohnküche)
Schlafen Eltern12–1415–1818–24 (+Ankleide 5–8)
Kinderzimmer10–1212–1515–18
Arbeits-/Gästezimmer9–1112–1414–18
Bad ( Eltern, Wanne+Du+WC+2 Waschtische)5.5–6.57–910–14
Bad (Kinder, Du+WC+WT)4–55.5–77–9
Gäste-WC2.2–33–44–6
Diele/Flur (EG circulation)6–99–1414–20
Hauswirtschaftsraum (HWR, waschen+heizen)5–67–910–14
Abstellraum2–33–55–8
Treppenhaus WF-Anteil (EG+OG combined)8–1111–1414–20
Technik/Anschluss (within Keller or HWR)3–55–88–12

All areas in m² (Wohnfläche logic: 100 % floor area; under a DG slope floor with a clear height of at least 2 m counts in full, between 1 m and 2 m at half, below 1 m not at all — Wohnflächenverordnung, T2, VERIFY when the number is sold as WFL; §3.4).

The gap between 3.1 and 3.2 is the point. 7.5 m² is not a German bedroom — it is a child's room from the 1960s. Quote 3.2 to clients; keep 3.1 only to defend a squeeze.

3.3 Furniture-driven minimums (why 3.2 is what it is — universal geometry)

Bedroom — German bed formats 180×200 / 140×200 / 90×200. Clearance (Neufert-lineage, T4): side circulation 750 comfortable / 600 absolute one long side, 600 the other; foot-of-bed to swinging wardrobe 900 (700 sliding/no door); Schrank 600 deep + 900 standing zone. Minimum workable parents' room: 1.80+0.75+0.60 = 3.15 m × 2.00+0.90+0.60 = 3.50 m ≈ 11 m² clear → why 12–14 m² is the compact market floor, 15–18 comfortable.

Kitchen — counter 600 deep, wall cabinets 350–400; aisle 1000–1200 (two-cook 1200+); work-triangle perimeter 4.0–8.0 m; island needs 1000+ clear all working sides; dishwasher door + 900 in front; German kitchen sill standard 1000 mm over a 900 counter.

Bathroom — WC 600 mm side clearance to obstacle, ≥500 (comfort 600) front (DIN 18040-2 accessible = 900×1200 + side transfer — route accessibility-universal-design); Waschtisch ≥500/700 front; Dusche 90×90 min, 100×120 comfort, bodengleich = value + ageing; minimum honest 3-fixture bath 1.8×3.0 ≈ 5.5 m² — below that, split the WC out.

Dining — 600 per seated person, ≥900 behind chairs to pass (700 to pull out); 6-seat 1.60×1.90 + 0.9 all round → 9.2 m² core, the 12–16 band adds circulation overlap + sideboard.

Wohnen — 3-seater + armchair + TV wall ≈ 3.5×4.5 m clear minimum liveable (16 m² hard floor); 25–35 m² is the norm because German Wohnen also carries the Essplatz or a desk corner.

Where these numbers come from: every clearance above is a derived rule; the raw anthropometric body-posture and reach envelopes underneath it (the actual Neufert "little man" pages) are tabulated in 3.9 — use that table when a brief squeezes a clearance below what's printed here and you need the body geometry it will violate, not just the market convention.

3.4 Ceiling heights and floor-to-floor (German defaults)

SpaceLBO-ish floor (T2, VERIFY per state)Market practice (T4)
Wohnräume≥ 2.40–2.502.60–2.80 (KfW-efficiency houses often 2.60–2.70 to cut envelope volume)
Bad/HWR/Flur—2.30–2.60 (often lowered for installation level)
Unterzug clear at escapes/doors≥ 2.00 (MBO lineages, VERIFY)keep ≥ 2.10

Attic storey under a pitched roof (Dachgeschoss, Kniestock/Drempel). The knee wall is the outer wall along the eaves that rises above the attic floor before the roof starts; it lifts the slope and with it the floor one can stand on. Under the slope the clear height falls towards the knee wall, so a room there has no single height. Bavaria asks 2.40 m clear for a habitable room, in the attic 2.20 m over half of its floor, where parts lower than 1.50 m are not counted; this does not hold for habitable rooms of residential buildings of classes 1 and 2 (S.1). For the living area, floor under a clear height of at least 2 m counts in full, between 1 m and 2 m at half, below 1 m not at all (Wohnflächenverordnung, T2, VERIFY). A local design statute may cap the knee wall (S.4); how the model draws one: S.3.

A flat ceiling under the ridge (Kehlbalkenlage, Decke zum Spitzboden). Often the attic rooms are closed at the top by a flat ceiling between the two slopes, at the level of the collar beams that brace the rafter pairs (S.4); the triangle above it is a loft (Spitzboden). A room's clear height is then that ceiling in the middle and the slope at the sides, and the rules above count its floor by both. A loft without a habitable room may be reached by a folding stair or a ladder in buildings of classes 1 and 2; a usable roof space otherwise needs a stair (S.4). How the model draws such a ceiling: S.3.

Dormers and roof cut-outs. A dormer lifts the slope over part of the attic floor and gives it a window in an upright wall; a roof cut-out opens the slope to an outdoor terrace in front of a rear wall (roofing-waterproofing §11.4). Under a dormer the clear height is that of the dormer's roof, and that floor counts by it in the rules above (S.1); the floor of a cut-out is outdoor space like a loggia (3.10) and is no part of the room. Whether a town allows them, how wide and how far from verge and ridge, is local law (roofing-waterproofing S.6).

F2F default: clear 2.70 + RC buildup 0.20 (or timber 0.30–0.38) → F2F 2.90–3.05; use 2.90 as worked default. Every +100 mm costs façade, stairs and (on many plans) the next Vollgeschoss reading — check 1.4 first.

3.5 Program elements the German market expects (T4) that foreign manuals omit

Omitting these reads as amateur on a DACH resale:

ElementWhat it isPlanning rule
Gäste-WCHalf-bath off Diele2.2–4 m², window or Belüftung, NOT off the open Wohnbereich sightline; under-stair location classic (headroom rule 5.2)
HWRHauswirtschaftsraumwasher+dryer+boiler/heizung+circ pump; adjacent to kitchen and to the Keller stair; stack wet-on-wet (9.1)
Kellertreppe within Dielebasement accessinside the thermal envelope; landing ≥ door width; headroom to door
Abstellkammerpantry/storage near kitchen or Diele2–4 m² at 350–400 depth fits the vacuum/shelves
Hausanschlussutility entry (Strom-KH, Wasser, Abwasser revision, Telecom, PV backup)1.0–1.5 m² wall of the Diele/Keller; NEVER a finished room's wall face; coordinate building-services-tga
Geschossübergang TGA-Schachtstacked wet/installation duct9.1
Kaminofen / herdstove flueearly: flue line through floors + roof, non-combustible floor zone — route building-services-tga/fire
PV + Speicher/Wallboxenergyroof zoning (9.6) + wallbox circuit at Stellplatz
Gartengeräte-/Fahrradraumgarden/storage4–8 m², external door, floor drain; plan vs GRZ (annex counting!)

3.6 Bedroom count and unit mix heuristics (T4)

Bedrooms = parents + 1 per child + guest/office if space (+1 Arbeitszimmer
per remote-working adult, or double-duty guest).
EFH/DHH family (2+2): 3–4 SZ + 2 Bad + GWC + Wohn 30–40 + offenes Koch-Ess
→ WFL 110–145 → gross ×~1.35 (walls/stair/Flur) → 150–195 m² → at placeholder
GRZ 0.4 needs two storeys from ~300–350 m² plot up (Section 2.2 math).
Single/2-person ("Seniorengerecht"): 2 SZ + barrier-leaning Bad + Wohn-Koch
35–50 → EG-only or 1.5-storey.
DHH: EFH × ~0.85; mirror with the neighbour — stair + wet zones on the party
line so each half's baths sit on baths (9.1).
MFH (3–8 units) market bands (VERIFY local demand): 1-ZKB 32–45 · 2-ZKB 52–65 ·
3-ZKB 68–85 · 4-ZKB 88–110 m² WFL; every unit 2 aspects or corner
(single-aspect only ≤ 50 m²); depth/economics → `building-typology`.

3.7 Parking (Stellplatz — dimensions + the GRZ trap)

  • Bay 2.50×5.00 min / 2.75×5.50 comfort; SUV 2.75×6.00; between adjacent

cars +0.75 for doors (garage box 3.0×6.0 single / 5.0×6.0 double class).

  • Garage clear height ≥ 2.00 under the door; sectional heads 300–500 (product).
  • Drive ≥ 3.00 m; reversing into a 2.5 m bay from a 5 m drive needs ~6 m

behind — on narrow plots make it one-way or pull the garage INTO the house (hits GFZ-free wall area, spares GRZ paving).

  • **Every paved m² is GRZ money (1.3): count Stellplätze FIRST, then design

the house with what remains.**

3.8 Area budgeting — does the brief fit the envelope?

Do this before drawing anything. Arithmetic; two minutes; prevents the classic failure: a plan that "fits" only because every room was quietly shrunk 12 %.

STEP 1 Available gross above-ground = A × GFZ (Section 2 — PLACEHOLDER
figures; re-run with the
parcel's own plan)
STEP 2 Available usable (NRF/WFL) = gross × NTG (Section 10.2 targets)
STEP 3 Required = Σ T4 room areas (3.2) + circ allowances
STEP 4 Compare:
Required ≤ 0.95 × Available → comfortable, proceed
0.95–1.05 → tight; lose a store or a room NOW
> 1.05 → does not fit. Resolve:
(a) drop/merge a room (b) DG/Renaissance if height clause allows
(c) Keller (GFZ-exempt? plan-text law — VERIFY)
(d) bigger plate via different plan zone / §34 argument

Worked — the generic 600 m² family brief (4-person household):

Envelope (placeholders): gross above-ground = 600 × 0.8 = 480 m²
NTG 0.75 → usable ≈ 360 m² over 1.5–2 storeys.
Required at T4 (comfortable band): Wohnen 32 + Essen 14 + Kochen 12 +
Eltern 16 + Ankleide 6 + 2× Kinder 13 + Arbeits 12 + Bäder 8+6 + GWC 3 +
HWR 8 + Abstell 4 ≈ 137 m² of rooms + Diele/Flur 14 + Treppe 12 ≈ 163 m².
Ratio 163 / 360 = 0.45 → fits on TWO floors with ~55 % margin — but the real
binding constraint here is GRZ (house footprint + ALL paving, 1.3) and the
height clause (DG legality), not GFZ area. Client summary: "floor area is
legal; the ground is the limit." If the brief had scored > 1.05 instead,
that would be resolved HERE (drop/merge/plot), never by shrinking every room.

Rule: when a brief scores > 1.05, put this arithmetic in front of the client in exactly this form. It converts a taste argument into a numbers argument, and the numbers win.

3.9 Anthropometric basis — body dimensions and movement envelopes (T4, Neufert Measurement-Basis chapter)

3.2's room bands and 3.3's furniture clearances are derived numbers. This subsection tabulates the primary anthropometric data they were derived from — the "Man: Dimensions and Space Requirements" plates of Neufert's Measurement-Basis chapter (2002 English edition, pp. 16–17; the classic "little man diagram" lineage referenced generically at 3.3 and in the tier table, Section 0). These are body-and-movement geometry, not a DIN standard and not German law — where DIN 18040-2 (barrier-free) requires a larger clearance, DIN 18040-2 wins; route accessibility-universal-design. Use this table when a brief pushes a clearance below the 3.2/3.3 market band and you need to show the client the body it will no longer fit, not just the convention it violates.

Static body-posture envelopes (p.16, figs 1–12 — average adult, normal dress):

PosturePlan envelopeHeightPlanning use
Standing, arms at side (profile)300 mm—baseline silhouette; cf. Modulor 1.75 m figure (Section 0/p.15)
Standing, arms akimbo / hands on hips875 mm—dressing-area, WC-cubicle sizing
Standing, one arm raised overhead875 mmreach to 1.50–1.75 mwall-cupboard top shelf
Standing, both arms spread sideways1125 mm sweep (500 mm shoulder box)to 1.75 mwardrobe/workbench full-reach arc
Bending forward, hands to floor875 mm1.375 mbed-making, cleaning-access strip
Kneeling upright, sitting on heels875 mm1.00 mfloor-level storage/work
Squatting, full crouch625 mm—low-shelf/low-cupboard access
Sitting cross-legged on the floor750 mm0.875 m—
Sitting cross-legged, upright700 mm1.125 m—

Furniture-envelope dimensions (p.16, figs 13–20):

Item / taskPlan footprint or reachHeightsCross-ref
Work table, seated875 mm widthseat 450–480; table 750–800; overhead reach 1350validates 3.3's desk/table sizing
Dining/side chair, pulled out875 mm depthseat 400–450; back 750≈ 3.3's dining "≥900 behind chairs / 700 to pull out"
Small easy chair900–1000 mm depthseat 375–400; arm 600; back 700Wohnen seating footprint (3.2's 25–35 m²)
Armchair1250 mm depthseat 250–350; arm 625—
Standing work-counter, forward reach660 mmcounter 900; overhead shelf 1500; standing eye ~1930validates the 900/1000 mm kitchen-counter/sill pair (3.3)
Kneeling reach (low unit)710 mm depthreach band 460–1220
Seated reach860 mmto 1450
Squatting reach710 mm300–1020

Bed and sleeping-zone envelopes (p.16, figs 21–24 — read together with 3.3's bed-clearance arithmetic):

Activity at the bedZoneClear heightCross-ref
Sitting on the edge, reaching a bedside shelf1250 mm875 mm to shelfunderlies 3.3's foot-of-bed 900 mm swing zone
Reclining, reading1500 mm750 mm to any overhead obstructionheadboard-side shelf clearance
Sitting up in bed1625 mm625 mmmatches a 1.60 m-wide bed + one-side reach
Lying full length, arm extended2000 mm envelope; 1875 mm clear length; 300 mm past the feet—sets the minimum clear depth behind a bed at ≈2.0 m, before 3.3's 750/600 mm side clearances are even added

Circulation and passing widths (p.17, "Space Requirements" plate — captioned explicitly: "for moving people, add >10 % to widths"):

ConfigurationWidthDACH cross-ref (this skill)
One person, sideways/profile375 mm—
One person, facing625 mm≈ the T3 absolute-floor corridor width (4.1)
One person, arms akimbo875 mm—
Two people passing1000 mm= the T4 "Flur serving 1–2 rooms" 1000 mm width (4.1)
Two people abreast1150 mm≈ the 1100–1250 mm "Flur serving 3+ rooms" band (4.1)
Three people abreast1700 mmDiele/entrance-hall scale (4.4's 1400–1800 mm)
Four people abreast2250 mmpublic-corridor/landing scale, not residential Flur
Closely packed standing row1250 mm/person-rowcrowd reference only
Waiting queue2125 mm—
Pace length, walking in step750 mmstride cross-check against the stair tread band (5.1, 260–300 mm)
Reach, kneeling down1125 mmunder-stair storage clearance cross-check (5.2)
Reach, standing at full stretchto 2250 mmceiling/top-shelf planning
Person carrying one case800–1000 mmDiele shoe/coat niche depth (4.4)
Person with an open umbrella (two together 2375 mm)1125 mmentrance canopy / vestibule depth (7.5 Windschutz)

Reading it for this skill: none of this table overrides 3.2's market targets or 4.1's Flur widths — it is the body-geometry floor those numbers were built on, and it is what to show a client who wants to cut a passage to 700 mm or a bed clearance to 400 mm: below the one-person-facing envelope (625 mm) or the two-people-passing envelope (1000 mm), the room stops working as a room, independent of any code minimum. Cite as: Neufert, Architects' Data (2002 English edition), p. 16 (body measurements/ furniture) or p.17 (space requirements/circulation).

3.10 Outdoor space on a storey — loggia, balcony, roof terrace

A loggia is a covered outdoor space recessed into the outline of the house: walls on the sides it shares with rooms, open on the others. A balcony projects beyond the outline; a roof terrace lies on the roof of a room below. All three are outdoor space, not rooms: not heated, not habitable, no daylight or minimum-area rule of their own.

  • Envelope. The walls between an outdoor space and a heated room are outer walls

of the thermal envelope (building-physics-thermal-moisture); the open sides get no wall. A window or door onto a loggia is a window or door to the outside.

  • Floor. The floor of a loggia is an ordinary floor slab, carried like the others

(structural-systems), for the imposed load of category Z (roofing-waterproofing §8, S.4). Over a heated room it is that room's roof: insulation, waterproofing and falls as on a flat roof (roofing-waterproofing §8). A slab that runs from inside the envelope out into a balcony is a thermal bridge and needs one of the breaks of construction-detailing §4.7; a loggia inside the outline needs none of them when its floor is insulated on top as a roof.

  • Guard. Every open side gets a guard, a parapet or a railing, where the floor lies

more than 0.50 m above the ground or the surface below (Bavaria, BayBO Art. 36; stairs-vertical-circulation S.3). Its height comes from the same section: 0.90 m for a fall height up to 12 m, 1.10 m above. The law of the state decides.

  • Depth. Usable depth at least 1.50 m from the wall to the guard (S.3, a default of

this library; no book gives a depth).

  • Counting. Outdoor space is listed apart from the living area: the

Wohnflächenverordnung counts balconies and loggias at a quarter, at most a half (building-typology). For GRZ/GFZ the plan text decides (1.4). The window rule of a room behind a glazed loggia counts the loggia's floor with the room's (S.1).

  • Distance to the boundary. A loggia lies inside the outline and is measured with

the house; a balcony may stay out of the setback depth only within the limits of the state law (S.2).


Section 4: Circulation — Flurs, Doors, Windows

Circulation in a well-planned German house should be 8–14 % of gross covered area. Over 18 % means the plan is fighting itself — usually a misplaced stair or a Flur serving two doors.

4.1 Passage (Flur) widths

SituationAbsolute floor (T3)German practice (T4)Recommend
Any residential corridor900 mm—never below
Flur serving 1–2 rooms90010001000 mm
Flur serving 3+ rooms / main9001100–12501100–1250 mm
Diele (coat + pass-through)9001200–18001400 with 600-deep wardrobe wall

Body geometry behind these widths: one person facing = 625 mm, two people passing = 1000 mm, two abreast = 1150 mm (Neufert space-requirement plate, add >10 % for movement) — see 3.9 for the full anthropometric table this and 3.3's furniture clearances are built on.

Mechanics: widths are finished-surface to finished-surface (frame rough +30–60 mm); keep 1200 mm + 885 clear doors as barrier-free reserve (90° turns need more — accessibility-universal-design, DIN 18040-2 binding only if claimed).

4.2 Doors (T2/T4 — legacy DIN 4161 leaf vs DIN EN 101 light widths; pick one family, VERIFY)

DoorLeaf (mm)ClearNotes
Eingangstür EFH1010–1135~900–1000side light widens
Room doors861–986 (legacy) / 835–985 (DIN EN 101)~710–875985/885 class = resale standard
Bad / HWR / Abstell611/736~585–710outward or sliding under 4 m² baths (fall-inside blocked-door logic)
Kellertür861–985≥800 + landing
Terrasseelement ≥ 2.40—slide/lift 2–3 m = value move

4.3 Window and opening sizes (T4 practice; geometry universal)

OpeningTypical W×H (m)Sill (m)Notes
Schlafzimmer1.2–1.6 × 1.250.80–1.00openable sanity + escape (4.5)
Wohnen2.4–3.6 × 1.75–2.250.40–0.60low sill = garden sightline; fall-guard duty at ≥0.5 sill states vary (VERIFY)
Kücheband over counter1.000.90 counter + 0.10 splash
Treppelanding window0.90–1.20stops the unlit-stair defect
Bad0.8–1.2 × 0.6–1.01.60–1.90privacy; openable in practice
Keller-Lichtschacht≥ 0.8 × 1.2 clear—doubles as cellar-room egress!

Window head: align with the door-head band (2.00–2.25 finished) → one lintel line, calmer façade, continuous shading line (7.3).

Size first: the rough opening of the windows is at least 1/8 of the net floor area of the room (MBO § 47, S.1); the openable 1/10 below is the second, weaker test. Two arithmetic traps: 1. Openable ≥ 1/10 floor-area bites on big rooms — 32 m² Wohn, 2.4×1.75 glazed → openable half = 2.1 m² = 6.6 %; add a second leaf; compute. 2. Sliders halve openable; Kipp is not full ventilation. DG roof-window rooms pass air but pay summer overheating (7.3/7.4): the digest's S-index + F_C table (Raffstore ≈ 0.25–0.35 external) prices the fix — proof: building-physics-thermal-moisture.

4.4 Entrance sequence (Diele)

Diele ≥ 5 m² (8–12 comfort). Visual break front door ↔ Wohnen (wall turn, cupboard screen, closed door) — the "man sieht beim Öffnen alles" complaint is the privacy rule; Gäste-WC off the Diele, never through the family zone; a 350–400-deep shoe niche at the door — universally needed, never built.

4.5 Egress logic (T2/T3 — VERIFY state versions, building-regulations-permits)

  • MBO-lineage: every storey needs first + second Rettungsweg; within dwellings

the escape class is met by openings ≥ 0.90 × 1.20 m clear — a normal 1.2×1.25 casement passes, a 0.6 m bathroom window does NOT and is no escape.

  • Rauchwarnmelder Wohnräume/Flur/DG (state duty incl. existing — VERIFY).
  • Never lock the only stair inside the kitchen/cellar room. DG: passable escape

window per sleeping room, reachable sill (figures = state/fire, VERIFY).


Section 5: Staircase — Geometry and Placement First

5.1 The bands (T2 — MBO §35 family; state LBOs amend, VERIFY)

ParameterGeneral (MBO-derived, VERIFY)Within dwellingComfort target
Riser S140–180 (up to 190 legacy)≤ 190160–180
Tread A250–300≥ 210–230 floor260–300
Comfort rule2S + A = 620–640
Clear width≥ 1000 common stairs≥ 500 legal floor (!)900–1100
Headroom≥ 2000≥ 2000≥ 2100
Risers per flight≤ 18land at ≤ 12–15
Landing≥ flight width≥ 1.0 m + turn
Handrail / balusters≥ 900 (fall duty, state-VERIFY); no climbable pattern; sphere ≤ 120 (applied 10 — VERIFY)both sides > 1100

Never quote the 500 mm legal floor as a target — the market sells ≥ 850 and a sofa must pass.

5.2 Worked stair calculation (default EFH stair)

F2F 2900 (2700 clear + 200 slab, 3.4)
Risers: 2900/170 = 17.06 → 17 R @ 170.6 ✓ band
Treads: 16; comfort 620 − 2·170.6 = 278.8 → A = 280 ✓
Straight: 16×280 = 4480 → needs a 4.6 m wall run (whole room length on row plots)
Dog-leg ½-Wendung: 9+8 risers; 8×280 + Podest 1100 = 3340 run ×
(2×900 + 200 well = 2000 wide) ≈ **3.34 × 2.0 m slot** — the "Treppe needs
2 × 3.5 m" figure is arithmetic, not convention.
  • Odd split 9+8 fine; one riser height everywhere (#1 trip + claim cause).
  • F2F 3.05 → 17 R @ 179.4, 16 A @ 261 — taller storeys eat stair length.
  • Headroom, the skipped check: at the half-landing, clear = F2F/2 − slab −

finish = 1450 − 250 = 1200, +170.6/tread → 2000 cleared 5 treads back from the landing nosing. A 3-tread under-stair store will hit heads; the under- stair Gäste-WC needs ≥ 2 m over the whole fixture+move zone — usually the upper flight's underside, not the lower.

5.3 Type selection

TypeSlotUseAvoid
Straight flight1.0 × ~4.6 mlong row segment, side wallshort plots
Dog-leg~2.0 × 3.4 mdefault EFH/DHHslot < 2 m
Quarter-turn~2.1 × 3.5 mDiele cornertight plots
Open well+0.3 mshowpiece, lightsmall houses; acoustics → building-acoustics
Winders (no landing)1.0 mlast resortchildren/elderly; MBO width conditions VERIFY
SpiralØ1.6–2.0cellar/bonus stairprimary — furniture cannot pass

5.4 Placement rules

  1. Stack exactly (misaligned = slab cut + transfer + void).
  2. Land in circulation on both floors, never in a bedroom.
  3. On the party/gable side in row/DHH — a central stair splits a 5.5–6 m

living zone in half.

  1. Light it: landing window to gable/shacht, or rooflight over an internal

eye — the unlit stair is serial housing's most common defect.

  1. Under-stair space only with 5.2 headroom math.
  2. Separate-let unit (Einlieger/Zweitwohnung): its stair must be reachable

without crossing the main unit — decide before the first sketch; also own Stellplätze + "number of Wohneinheiten" allowed by the plan (VERIFY).


Section 6: Sun Geometry, Courtyards and Light Wells

6.1 Solar altitude — the formulas (T5: geometry, exact for noon sun)

Noon sun altitude from latitude φ (declination ±23.44°, used as 23.5 here):

summer solstice (21 June): h_s = 90° − φ + 23.5°
equinox : h_e = 90° − φ
winter solstice (21 Dec): h_w = 90° − φ − 23.5°
courtyard W/H needed for winter noon sun to reach the floor = 1 / tan(h_w)
horizontal overhang to fully shade a south window of height H at noon:
D = H / tan(h) (shadow drop = D·tan(h))

Applied to DACH cities (the geometric consequence of latitude — this table replaces any city-specific handbook table; regenerate for any other site):

Cityφh_s (Jun)h_eh_w (Dec)winter W/H for sun to floor
Berlin52.5°61.0°37.5°14.0°4.01
Hamburg53.6°60.1°36.4°12.9°4.36
Frankfurt50.1°63.4°39.9°16.4°3.40
München48.1°65.4°41.9°18.4°3.01
(Wien ~48.2°, Zürich ~47.4° — same math)

The honest DACH conclusion (inverts the hot-climate courtyard logic): at ~14° winter noon sun (Berlin) a court needs W/H ≈ 4 for sun on its floor — a 2-storey court (H ≈ 6.4 m) needs ≈ 26 m width; sun onto the north wall at 2 m floor height still needs ~17.6 m; single-storey (H 3.3) ~13.2 m — garden scale, not courtyard. So the garden + south facade do the winter-gain work; an Atrium/Hof is chosen for daylight, privacy and outdoor value, accepted as winter-shadowed (heating penalty = building-physics-thermal-moisture); summer shading is mostly a morning/evening/oblique-sun task since 60–65° noon sun already clears most horizontal devices.

6.2 Sizing bands (retagged for the heating-dominated climate)

TypePlan sizeW/H at 2 storeysFunction
Lichtschacht (light well)1.2×1.2 up to 2.0×2.5< 0.35bath/stair/cellar ventilation + code light only — call it that, not a courtyard
Lichtof / narrow air shaft between row gardens1.5–3 m wide slot0.3–0.6daylight to a side room, borrowed air; privacy-glass
Small court (Sitzhof, Vorgartenhof)3×4 – 4×50.6–0.9usable outdoor room off the Diele; wind shelter; the DACH value move on a 5.5–7 m row segment
Atrium / Innenhof of MFH8×10 up1.2+daylight to inner units; diaphragm-cut flag (2.6); winter sun irrelevant, summer self-shade pleasant

Aspect: 1:1–1:2 (long axis E–W for midday sun on the north face); <0.3 = shaft; >1.2 = yard, not court.

6.3 Making the court actually work in DACH

  1. Drain and frost-proof it: slope ≥ 1:50 to a frost-protected drain

(Entsorgungssatzung/Rückstau considerations — route building-services-tga); never toward the house; a court below the backflow level (Rückstauebene) needs a Hebeanlage — hard legal+physical check, VERIFY with the Entwässerungsgenehmigung.

  1. Glazing it (Wintergarten/Loggia) makes a heat buffer but changes

GRZ/GFZ/Abstandsflächen counting — plan text, VERIFY.

  1. Openable connection to every surrounding room — night purge of the mass

(Nachtabkühlung, 7.5/DIN 4108-2) is the summer half of the mechanism.

  1. Plant/water at least partially — an all-paved court is a GRZ-counted

heat radiator (1.3) with nothing to show.

  1. Overlooking: stagger sightlines / partial screens (neighbour privacy

claims under Nachbarrecht are real design constraints — VERIFY).

6.4 Light wells and windowless rooms

  • Internal bathrooms need mechanical Lüftung (WRG/extract): "Fensterpflicht"

is habit, not law — windowless Wohnräume are LBO-possible with proper ventilation/light, but market + lenders punish them (T4, VERIFY financing).

  • Shaft depth: below ~1:6 W:H delivers daylight, treat as light + vent; design

the artificial light regardless.

  • **Never cap a shaft that serves as a second escape route or a cellar room's

only opening** — the opening must stay passable (≥ 0.9×1.2 clear class).

6.5 Court vs light well vs none — decision tree (DACH)

Is there ≥ 3.5 m of spare plan width after the room budget (3.8)?
└─ NO → Lichtschacht or none. Mechanical bath ventilation. Stop.
└─ YES ↓
Is the plan deep (>14 m) without a garden aspect on two floors?
└─ NO → none; daylight the Flur from the Diele/OG slot instead.
└─ YES ↓
Row/DHH segment with 5.5–7 m width?
└─ YES → SITZHOF 3×4 off the Diele or between house and garage (the classic
Reihenhaus "Vorhof/Innenhof" move) — privacy + daylight + the value
of an outdoor room; winter sun not promised.
└─ NO (MFH / deep free-standing) → ATRIUM/HOF, centred (2.6 diaphragm flag),
edge beams all four sides, ≥ 1:1.2 plan, E–W long axis;
inner units' windows onto it: acoustic reflection check
(`building-acoustics`) + overlooking check 6.3(5).

Section 7: Orientation, Sun, Wind and Noise (DACH)

7.1 The headline

DACH is heating-dominated: the free moves are capturing low winter sun on the south facade, excluding summer sun, and night purging (DIN 4108-2 sommerlicher Wärmeschutz, climate regions A/B/C + S-index — both in the digest; a room failing S ≤ S_zul is a legal Nachweis problem later, so fix orientation early — formal proof: building-physics-thermal-moisture).

Core rules:

  • Long glazed facade south (±~45° acceptable before gain drops off — SE/SW

still good; multiple E/S/W-glazed rooms worsen the S-index, digest design heuristic).

  • East/West: real but manageable (low-angle sun; vertical shading works;

the hot-country "zero west glazing" rule does NOT apply — in DACH a west terrace is a valuable summer-evening asset if shaded).

  • North: daylight without gain — put unheated/buffer rooms there

(Garage, HWR, Abstell, Treppe), exactly the old buffer logic, rotated 180°.

  • Roof = biggest gain surface (digest roof-window S-terms/tilt factors);

PV south 30–36° (yield band — verify with a calculator); roof zoning 9.6.

7.2 Room-by-room orientation (retargeted table)

RoomBestWhy
WohnenS / SWwinter gain + garden; deep overhang/balcony for summer
Essen/WohnkücheS–SEmorning-to-day light
SchlafzimmerO / NO / SOmorning warm, afternoon cool (sleeping = coolest room preference)
KinderSE/Olight; avoid W (late heat → bed-time)
ArbeitszimmerN–NW acceptablediffuse light, less glare; W needs shading
Badany daylight, often N
HWR/Küche-technik, Kellerabgang, GarageN / W stripbuffer principle
DieleN entrance typicalvestibule double-door mitigates winter drafts
TerrasseS/SWthe value facade
Sitzhof/Atriumcentre6.x

7.3 Winter vs summer contrast — the worked shading numbers (T5 geometry)

South window, height H = 2.1 m (living, near-flat roof shading line):

München: h_s = 65.4° → D = 2.1 / tan(65.4°) = 0.96 m
shadow drop at winter h_w = 18.4°: 0.96 × 0.333 = 0.32 m
→ 1.78 of the 2.1 m in full winter sun ✓ — one 0.95–1.00 m balcony
slab/roof projection is a complete seasonal solution.
Berlin: h_s = 61.0° → D = 2.1 / 1.804 = 1.16 m; winter drop 0.29 m → 1.81 m
of sun ✓. Same logic, deeper projection (≈ roof-overhang or first
balcony plate).

Same window, west, July ~18:00 (altitude ≈ 25–30°): D = 2.1/tan 27° ≈ 4 m — no sane horizontal overhang shades a west window. Working devices: vertical fins, Raffstore, loggia recess, planting — or move the window. The digest's F_C table prices them for the S-index proof (external Raffstore 45° 0.25–0.30; canopies 0.50–0.55; roller ¾-closed 0.30–0.35) — formal Nachweis: building-physics-thermal-moisture.

7.4 Facade glazing strategy (WWR — retagged; DACH is a balance, not a

minimisation)

FacadePractical bandLogic
S25–40 % of that wall, shadedwinter gain is wanted; unshaded S glazing becomes a summer liability (S-index +0.10 term for N-share, F_C table)
O/W10–20 %, device-shadedlow-angle; fins/Raffstore/loggia
N10–20 %daylight only; keep on buffer rooms
DG roof windows≤ ~15 % of floor, g_tot lowoverheating risk class; openable + shading mandatory in practice

(These are design bands, T4/T5-flavoured; the legal check is DIN 4108-2 S ≤ S_zul per room, with the digest's S_1…S_6 terms — building-physics-thermal-moisture.)

7.5 Wind, climate-adaptive notes (replaces the hot-country wind-rose tables)

Wind exposure is local (coastal Hamburg vs Alpine foreland vs Oberrheingraben, neighbour shelter, terrain, B-Plan plantings) — apply generically:

  • Summer comfort = Nachtabkühlung: night purge through the mass (the digest

S_1 table prices night-vent classes n≥2 / n≥5 h⁻¹); openable low windward, high leeward/stack via Treppe/Atrium; doors undercut 10–15 mm.

  • Winter comfort = vestibule/Windschutz or double door on exposed entries; n50

is a construction job (digest n50 ≤ 3 / 1.5 — building-physics-thermal-moisture).

  • Coastal/exposed sites: driving-rain exposure group III in the digest

(rainy/windy/coastal) triggers the façade-detail review — not a plan change.

7.6 Noise and privacy adjacencies (T2 — TA Lärm/DIN values, cross-ref

building-acoustics)

  • Street/mixed side: Diele, Treppe, HWR, Abstell, Garage as the acoustic

buffer before sleeping/living rooms (buffer principle again).

  • Quiet-side sleeping — digest TA-Lärm guide values: general residential

55/40 dB(A) day/night, pure residential 50/35; indoor protected rooms ~35 day / 25 night. A bedroom window to a street above night values cannot meet 25 dB(A) open → plan sleep-ventilation via the other facade or a Lüftungskonzept (DIN 1946-2, VERIFY); the Rw stack is building-acoustics.

  • Decide here: bedroom walls off the Diele/Treppenhaus side; bath pipes not

behind a shared headboard wall; Wärmepumpe-Außengerät position vs neighbours' bedroom windows (immission distance — a plan-position decision); Mischgebiet (1.2) trade noise — some newer B-Pläne carry "Lärmschutz / Raumanordnung" clauses: VERIFY plan text.

  • Overlooking: 6.3(5) + the 3 m-side habit → opposing windows ~6 m apart

(eye-contact distance); hedges/screens where the plan allows.


Section 8: House Typologies for German Plots

The archetype fixes structure, servicing, daylight and resale; the tree starts at Bauweise (plan law), then frontage, then brief. Depth → building- typology; here: plan consequences only.

8.1 Reihenmittelhaus / row segment (WR or closed WA)

Frontage 5.5–7 m, party walls both sides, garden axis fixed by plan; depth 11–14 m: 2-room band + 1.2 m stair/circulation strip; floor span = plot width 5.5–6.5 m (9.4, cross-wall logic); stair on one party side, full-width living to the garden; middle dark → Lichtschacht/Sitzhof (6.5); circ 12–16 %. The standard B-Plan product — you win on the section (DG? height clause!), not plan.

8.2 Doppelhaushälfte (DHH, offene Bauweise, one party wall)

Plot 250–400 m² (band), frontage 8–11 m, one open garden side. Mirror with the neighbour early: stair + wet zones on the party line, living to the open side; party wall = continuous cross wall (cheap). Best area-efficiency; detail the open-side reveals for the day the neighbour builds out (7.6).

8.3 Freistehendes EFH (offene Bauweise, both sides free)

Plot 450–700 m², frontage ≥ 12–16 m; 2–3-bay plans; usable garden is the S side — don't spend GRZ paving all round (1.3). Test 1.5-storey / 2 / 2+DG against GFZ AND the Vollgeschoss/Wandhöhe clause (a flat-roof DG often reads as 3 storeys on terrain where a Satteldach hides the same area legally — plan-text game, 1.4/1.5). This is the generic 600 m² case of Sections 2/12.

8.4 Zweifamilienhaus / two stacked units

Second entry must not cross the main unit (5.4(6)); two mirrored wet stacks, meters/tech per unit; the party floor is now a DIN 4109 legal-minimum case (unrelated dwellings — VERIFY state adoption) → building-acoustics; plan consequence: no stair beneath the other unit's Wohnen, buildup 300–400 class. Workhorse at GFZ ≥ 0.7–0.8 placeholders.

8.5 Kleines Mehrfamilienhaus (3–6 units)

Frontage ≥ 12–14 m or depth ≥ 25 m; units back-to-back on a Flur/Treppenhaus spine; reserve Aufzug ≥ 1.10×1.40 + machine space now (shaft = GRZ area — VERIFY vendor dims); every unit 2 aspects; Stellplätze under/on building (Tiefgarage shifts the Keller/GFZ reading — plan text). Depth on unit mix → building-typology.

8.6 Bungalow / slope variants

Bungalow: full GRZ at GFZ ≤ GRZ — check the clause isn't forcing 2 storeys ("min. 2 Vollgeschosse" exists in some WR plans — VERIFY) and roof/PV duties. Slope (Hanggrundstück): terraced full floors beat split levels (2.6 + cost — geotechnics-foundations); the walk-in downhill Keller is the German classic.

8.7 Infill / Baulücke (§34 read 1.7)

Match Bauweise, eaves line, roof form, window rhythm (1.7). Frontage fixed; narrow-front plans go sectional: stair one side, rooms single-loaded to the garden, Lichthof past 14 m depth (6.5).

8.8 Archetype selection tree

B-Plan Bauweise?
├─ geschlossen / WR ────────────→ 8.1 row segment (+Sitzhof 6.5). Stop.
├─ offen, "Einzel- u. Doppelhäuser" →
│ Frontage ≤ 11 m & client wants max area/unit ─→ 8.2 DHH (mirror stacks)
│ Frontage ≥ 12 m & one household ─────────────→ 8.3 freistehendes EFH
│ Two households / rental unit ────────────────→ 8.4 2-FH
│ ≥ 3 units wanted / GFZ ≥ 1.0 ───────────────→ 8.5 small MFH
├─ kein B-Plan (§34) ──→ 1.7 measure the surroundings, then match to their
│ Bauweise → re-enter the branch above.
└─ slope > ~5°? ───────→ 8.6 terraced variant of the chosen type (2.6 note).
Height clause (1.4) or GFZ (1.4) blocks the DG? → drop to 8.6 bungalow / 1.5-
storey before shrinking every room (3.8 rule).

Section 9: Stacking, Services and the Structural Grid

The house-scale core. A single house has no "core", but it has wet zones, a stair, installation ducts and column/wall lines — and they must line up.

9.1 The stacking rules

  1. Wet-on-wet. Every upper bath sits over a bath, kitchen, HWR or Flur —

never over a bedroom or Wohnen. (Universal; the leak-damage claim is the same in every market.)

  1. Kitchens stacked where two units exist; otherwise kitchen over

kitchen/HWR/garage.

  1. Stair stacks exactly (5.4).
  2. Wände tragen durch — a load-bearing wall stops at no floor without a

transfer beam (2–3× cost; house-scale, almost never worth it). Frame columns (if Skelettbau) run to foundation.

  1. Abwasser vertical: Installations-/Leitungsschacht stacked over the wet

zones; DN 100 per bath group; offsets with putztürmchen/revision. Gradients: DIN-1986-family practice ~1 cm/m for small lines, ≥ 0.5 cm/m for DN ≥ 100, self-cleansing band ~1:50–1:100 — T2, VERIFY current edition (digest sources carry none of it).

  1. Horizontal drain distance from furthest bath to stack ≤ ~4–6 m or the

floor buildup fights the heating/terrace level — the old "deep buildup" logic is metric and universal.

  1. Haustechnik stack: HT + Warmwasser on one wall (Keller/HWR); PV

counter/storage by the HWR; riser by the stair; gas only where a mains line exists (most new builds: none — building-services-tga).

  1. Fresh-air/WRG concept decides ducts early (KWL: duct runs in the

Deckenaufbau or along the Flur ceiling → ceiling-height loss; DIN 1946-2 VERIFY): reserve duct routes before the first room wall.

  1. Rainwater retention (cistern) often mandatory per municipality

(Entwässerungssatzung — VERIFY): reserve its Keller corner/garden strip now.

9.2 Typical 2-storey EFH stack (retargeted from G+1)

DG (if clause allows) 2–3 Kinder-/Arbeitszimmer + Bad; Kniestock logic (1.5)
OG Eltern SZ + Ankleide + Bad | 1–2 further SZ + Bad | Flur
EG Diele + GWC | Wohn-Ess-Koch open to garden | HWR |
(one guest/Arbeitszimmer SZ + Bad on EG — ageing-in-place:
most-requested, most-often-omitted item)
Keller HT + WRG + tanks + Hausanschluss | workshop | storage
(GFZ-exempt per plan wording — VERIFY 2.4)
Site Stellplätze, Zufahrt — ALL GRZ-counted (1.3)

9.3 Wall/buildup thicknesses (German, metric)

ElementBuildupNote
External masonry30–36.5 cm KS/brick + WDVS, or monolithic 36.5–42.5timber external wall 30–34 assembly
Load-bearing internal11.5–17.5 cm
Non-load partition (Trockenbau)75–100 mm + boards ≈ 100–125sound class → building-acoustics
Wet wall with DN 100 stack≥ 200 mm chase or Vorwand-Ständer + Verkleidung11.5 solid cannot take pipe + isolation
Decke RC180–250 + Estrich 50–65F2F 2.90–3.05 (3.4)
Timber deck / wood beam300–380 with diffusion layeracoustics + vibration — route
Putz/finish15–20 each face — deduct from clear dimsthe plaster trap, metric

FreeCAD default set (metric): exterior 365, interior 115, partition 100, slab 250, F2F 2900, door leaf 985/736/611 (885/611 light — pick a catalogue and stick to it), sill 900/1000, head 2095/2250, roof pitch per plan clause.

9.4 Structural-grid coordination (digest-supported — conception; verify

final with structural-systems)

The plan and the structure are decided together; rooms sized first and "the engineer will catch it" is how a Stütze ends up mid-bedroom.

DecisionPreliminary rulePlan consequence
cross-wall masonry (Querverband)floor spans = unit width, RC solid slab 5–7 m; timber ~4.5 m economic (conception)room widths ARE the grid; party + 2–3 cross walls line up through all floors
longitudinal band / Ständerfaçade columns 2.5–3.5× room bandsevery column inside a wall line; open side = the free façade
one-way slab depthspan/30, economical to ~8 m (~300 mm) (conception)6.5 m row span → ~220 mm class + buildup; > 7 m: two-way or beams (2-way action only ≈square, aspect ~1:1.5 → one-way behaviour — conception)
ring beam / Scheibeedge ring ≤ ~30× slab thickness; > 2 Vollgeschosse / length > 18 m / big openings trigger anchorage (conception — verify per Eurocode 6 national annex)continuous Flur-deck edge & gable tie; wall openings align
lintels over windowsflat brick lintel self-carries the triangle load zone; 24 cm wall spans ≤ ~2.0 m, 36.5 cm ≤ ~2.0–5.5 m without RC lintel (conception)window band width is a structural decision at ~5 m+ openings
non-load partitionsbuilt top-down, floor-deflection slot ≥ 10 mm, DIN 4103 line load 0.5 kN/m at 0.9 m (conception)bathroom walls on floating detail; never carry deck onto a partition
timber framestud grid 0.625 m (62.5/125 cm); panel formats to joints (conception 187–188)window reveals & Electo-routes land on stud rhythm — set room widths in multiples of 62.5
DG trussesKniestock height vs span; liveable band = ridge ≥ ~2.0–2.2 m — structural choice, routethe "hidden 3rd floor" (1.5) is won or lost on the truss

Rules: grid before furniture; grid lines = the continuous party/Flur/stair walls; rooms > 7 m wide are a structural decision (deck depth/two-way/beam); a court = diaphragm hole (2.6) — edge beam all four sides on grid; this table is preliminary — final members from structural-systems + the Tragwerksplaner.

9.5 Cross-reference — where this skill must NOT stand alone

This skill (a) flags plan-configuration risk originating here (2.6) and (b) tags every regulatory number VERIFY. It does not perform structural design, the Wärmeschutznachweis (→ building-physics-thermal-moisture), Schallschutz nachweise (→ building-acoustics), accessibility design (→ accessibility- design), or the authoritative legal read (→ building-regulations-permits: B-Plan text, state LBO/MBO §§, Stellplatz-/Abstandsflächen ordinance, GEG). Treat every GRZ/GFZ/Abstands number in this file as a placeholder to be replaced by the parcel's own documents — never as a citation.

9.6 Roof-level coordination: PV, flue, units, and the "Dach" clause

The roof hosts PV (S band 30–36°), flue line (must clear the PV field — route fire/services), HT/fresh-air terminals, service access — and some B-Pläne set PV zones on the roof drawing itself (VERIFY plan graphics!). Zone the roof in the model (PV / terminals / access / flue shadow) — Section 14 checklist slot.


Section 10: Efficiency — NTG and Circulation

10.1 Definitions (metric)

  • Gross (GRZ/GFZ language): areas to outer wall faces per the state's

calculation directive (VERIFY). NRF = room areas inside finishes; WFL = Wohnflächenverordnung bands (balcony 25/50 %, DG slope bands — VERIFY when sold/leased as WFL). NTG = NRF ÷ gross.

10.2 Targets

TypePoorTypicalGood
EFH/DHH 1.5–2 storeys< 70 %72–78 %78–82 %
2–3-unit house with common stair< 70 %72–78 %78–80 %
small MFH (8.5)< 68 %70–76 %76–80 % (Aufzug reserve eats it — plan the shaft once, 8.5)

Walls 8–12 %, circulation 8–14 % (§4), stair 5–8 % of gross. Efficiency is not the goal — Sitzhof and Diele score badly and buy real value; NTG catches waste (Flur with two doors, duplicated lobby, unstacked bath — 10.3).

10.3 German-specific leak list (trimmed)

Passage serving < 3 doors · stair mid-plan on a 6 m row · unstacked baths · two separate entrances where a combined Diele serves (two-unit!) · 11.5 walls where 10 Trockenbau carries nothing · a dead re-entrant corner from a bad stair · carport + full-length drive eaten by GRZ where an integrated garage would have hit GFZ for free · Wohnen under the unlit DG slope where a Kniestock would give full height (then the room is 60 % WFL per WoFlV bands — VERIFY).


Section 11: Legibility (Lynch, kept short)

  • Path: one clear Diele→Treppenhaus→Garten sequence; a guest never faces

three identical doors. Edge: the Diele threshold = public/private line.

  • District: guests front (Diele+GWC+Arbeitszimmer), family centre

(Wohn-Ess-Koch), sleeping quiet rear/OG, service band (HWR/Keller/Technik).

  • Node: Diele + stair landing — lit, visible from entry. Landmark: the

Treppenauge, a Sitzhof view, the open kitchen — one event orients the plan.

  • Front-door sightline must not reach a bedroom door; light passage ends;

height hierarchy Diele 2.70 > Flur 2.60 > lowered Bad/HWR — compression before the Wohnen makes arrival.


Section 12: Verification Checklist + Worked Example

12.1 Compute, don't eyeball — the model check list

  • [ ] Plot area/frontage/depth from the Kataster extract / Amtlicher Lageplan,

not satellite estimates

  • [ ] B-Plan figures transcribed with §-numbers (or §34 survey 1.7 attached);

any number still a placeholder = study marked non-submittable

  • [ ] GRZ: house + carport/garage + drive + paths + terraces **tallied from the

model**, ≤ A × GRZ (incl. any Minderanrechnung the plan grants — VERIFY)

  • [ ] GFZ: sum of storey gross areas ≤ A × GFZ; DG/Loggia/Keller counting per

plan text applied, not per habit

  • [ ] Height: storey count + Wandhöhe vs clause (1.4/1.5 measure line!)
  • [ ] Baufenster + Abstandsflächen: minimum boundary distances model-measured

(all 4 sides), incl. eaves/roof overshoot (many states count the roof projection into H — VERIFY)

  • [ ] Stair: riser/tread/2S+A computed from the real F2F; headroom ≥ 2000

checked under the flight; landings ≥ width

  • [ ] Every bath over a bath/kitchen/HWR; stacks model-traced
  • [ ] Bedrooms ≥ 10 m² (never below T3 7.5 m²); rough window opening ≥ 1/8 floor (S.1), openable window ≥ 1/10 floor,

openable counted; escape geometry per sleeping room (4.5)

  • [ ] Circulation % and NTG computed from areas, not vibes (10.2)
  • [ ] Court/Lichthof W/H stated (6.2 band) and not sold as winter-sun tech
  • [ ] S-index sanity: S-glassed rooms have a shading concept; DG rooms list F_C

device (7.3/7.4); formal proof = building-physics-thermal-moisture

  • [ ] Noise: sleeping rooms face the quiet side or have a Lüftungskonzept plan

(7.6); Wärmepumpe position checked vs neighbour bedroom distance

  • [ ] Plan regularity flags (2.6): L/court/wing/split annotated in handoff
  • [ ] Section 13 red-flag list run end to end

12.2 The generic 600 m² site — EFH, 4-person family (all plan figures

T1-V placeholders)

SITE 25.0 × 24.0 m = 600 m², street NW, garden SE. φ = 50° (generic central
DACH city → h_s 63.5, h_e 40.0, h_w 16.5 — recompute per 6.1).
PLAN WA, offen. GRZ 0.4 · GFZ 0.8 · "2 VGS, Wandhöhe bis 7.10 m, DG
zulässig (counts GFZ? → plan text: counts at 100 %? ASSUMED NOT fully —
PLACEHOLDER both readings, VERIFY)". Baufenster: 8 m street setback,
full side span; rear ≥ 3 m. Stp: 2.
ENVELOPE GRZ: 240 − (drive 30 + paths/carport-class 28 = 58) → house 182 m².
GFZ: 480. 2 floors × 182 = 364 gross; DG up to 480−364 = 116 gross
(≈ 80–90 NRF) fits the assumed reading. Height: 2×2.90 + DG within
7.10 wall + roof clause ✓ (measure-line check!).
SETBACKS A = max(3.0, 0.4×~6.5 = 2.6) → 3.0 m sides ✓ (long side 18.2 runs
parallel to the 25 m frontage ≤ 25−6 ✓; depth 10.0 inside the 8 m
Baufenster line + ≥3 m rear ✓; long facade faces the SE garden).
BUDGET usable EG ~150 + OG ~150 + DG ~85 → ≈ 385 NRF vs 163 m² room need
(3.8): FIT — binding constraint named for the client: GRZ/height, GFZ
has slack.
ARCHETYPE 8.3 freistehend; L-shape rejected (2.6 re-entrant + GRZ paving):
one 18.2 × 10.0 m block, long axis E–W parallel to the 25 m frontage,
garden side S. Plan depth 10 m → no Lichthof needed; Flur daylighted
from Diele + Treppe window (6.5: none).
ORIENT Wohn-Ess-Koch at SE facade, 2.1 m windows; summer h_s 63.5 → canopy
D = 2.1/2.01 = 1.05 m; winter drop 1.05·tan16.5 = 0.31 → 1.79 m lit ✓
(6.1 math). N strip: Diele, GWC, HWR, Treppe, Technik (buffer stack).
STAIR 17 R @ 170.6, A 280, dog-leg 3.34×2.0 well (5.2); window on landing;
stacked EG→OG→DG exactly.
STACK baths over baths on the stair wall; kitchen over HWR; WPL-Außengerät
N gable, off the neighbour-bedroom side (7.6); PV S band, flue N
corner (9.6).
ROOMS EG: Diele 12 · Wohn 32 + Ess 14 + Koch 13 (offen, together 55 clear)
· AR/Gäste 13 · HWR 8 · GWC 3 · Treppe 12 → gross 182 ✓
OG: Eltern 17+Ankl 6+Bad 8 · Kind 13×2 · Bad 6 · Flur 10 → gross 182
DG: Studio 30 NRF (Kniestock 1.2 — WFL bands per WoFlV — VERIFY) +
Abstell 8.
CHECKS GRZ: 182+58 = 240/600 = 0.400 ✓ (= placeholder exactly — re-run on the
real plan!) · GFZ: 364+~116 = ≤ 480 ✓ · NTG ≈ 0.77 ✓ · circ ~11 % ✓ ·
4.3 openable sanity per room ✓ · 2.6: rectangular, no irregularity
flag needed · escape windows each SZ ✓ · wet-on-wet ✓.
CAVEAT GRZ/GFZ/VGS/Wandhöhe/Baufenster/DG-counting/measure-line/GRZ-anrechnung
= T1-V placeholders — VERIFY against the parcel's own documents; study
for a Bauvorlagen professional, never one (Reality Check).

Section 13: Red-Flag Checklist (each = a recurring real defect)

#FailureFix
1GRZ tallied with house onlycount drive + paths + terraces + carport (1.3)
2GFZ "basement is free" assumedplan-text law; walk-out faces count (1.4/2.4)
3DG banked without height-clause readVollgeschoss definition + measure line (1.4/1.5)
4Bauweise ignored, detached drawn in WRtree starts at plan law (8.8)
5Built outside the Baufenster "just 40 cm"window is window; minor-annex list only (1.6/1)
6Abstandsflächen assumed 3 m everywhere0.4·H governs above ~7.5 m walls; state variants (1.6/3)
7Boundary garage/wall drawn without Grenzerleichterungstate cap + neighbour declaration (1.6/3)
8§34 drawn from vibesmeasured surroundings dossier (1.7) + Bauvorbescheid
9Brief never tested (3.8)the two-minute arithmetic
10Every room quietly shrunk to fitdrop a room; state it
11No EG room for ageing / guests9.2 kept rule — the most-omitted item
12Bad over Wohnenrestack wet-on-wet (9.1)
13Stair not stacked; different risers between runs5.2/5.4
14Unlit stairlanding window/rooflight (5.4)
15Under-stair WC with < 2 m head over the whole move zone5.2 headroom math
16Flur 850 mm "because code says so"market sells 1000–1250; 4.1
17Window sized by eyecompute rough opening ≥ 1/8 floor (S.1) and openable ≥ 1/10 floor; sliders halve (4.3)
18Winter sun promised to an Atrium floor at φ>48°6.1/6.2 math says no; reframe as daylight+privacy
19Lichtschacht sold as Innenhof6.5 naming honesty
20Atrium off-centre, edge beams "later"2.6/9.4: centre + continuous edge, flag engineer
21Court drains toward the house / no Rückstau check6.3(1)
22Sleeping rooms to the street, "windows stay closed in summer"7.6 buffer or Lüftungskonzept
23Wärmepumpe on the neighbour's property line7.6 immission distance
24PV laid before the flue/roof-clause check9.6 zoning + plan PV clauses
25Column stranded mid-room / 8 m span with 200 slab9.4
26Zweitwohnung stair crossing the main unit5.4(6)/8.4
27Circulation > 18 %misplaced stair first (10.3)
28A VERIFY placeholder quoted to client/authority as factsay "B-Plan-dependent, VERIFY" in the same sentence (Section 0)
29Output presented submission-ready / L/court/split handed off without the 2.6 noteReality-Check sentence + per-decision 2.6 annotation, unprompted

Section 14: FreeCAD / BIM Handoff

(Objects and code patterns: the FreeCAD/BIM skill of this library; what follows is the planning content to model and the hierarchy gotchas that bite.)

Confirmed inputs — 12.1's first boxes; then: plot as IfcSite from the Kataster outline in a local cartesian project system (origin near the object; UTM/ETRS89 ties via IfcMapConversion — digested geodesy practice; legal distances must hold in the real system), building under site, storeys above.

Storeys — the makeFloor gotcha (kept from the predecessor skill): Arch.makeFloor() — Elevation is derived from `Placement.Base.z`, not the reverse: setting floor.Elevation alone silently reverts on recompute. Set p = floor.Placement; p.Base.z = 2900; floor.Placement = p (mm → model units), then read back. Hierarchy: Site > Building > Storey(KG? EG, OG, DG) > Walls/Slabs/Stairs/ Windows; rooms as Spaces with freeArea/grossArea so GRZ/GFZ/NTG/circ% are scheduled from the model (12.1 = compute from data, never eyeball); storey gross sums give the GFZ reading, Elevation/height values drive the Wandhöhe check.

Dimensional defaults to set (from 9.3): exterior 365 · interior loadbearing 150 · partition 100 · slab 250(+50 Estrich shown in buildup) · F2F 2900 · door leaves 985/736/611 · heads 2095/2250 · sills 900/1000 · stair riser 170.6 / tread 280 · roof pitch per plan clause.

Verify in the model before presenting: everything in 12.1 is model-computable (area-plot the sealed surfaces for GRZ; boundary-offset the envelope for setbacks; schedule rooms for 3.1/3.2 floors) — plus: [ ] stair footprint identical per floor + DG eye [ ] roof zones (9.6) not overlapping flue/ladder [ ] the two VERIFY-marked readings of 12.2 (DG counts GFZ yes/no) both modelled so the client sees the consequence.

Then say it, per decision: "Planning model — not genehmigungsfähig; envelope figures are placeholders (list them); approval needs the parcel's Festsetzungen + Bauvorlagen signed by a Bauvorlageberechtigten (state LBO); Atrium/L/split items (2.6) need explicit Tragwerksplaner review."


Appendix A — Standards map (verify current editions; names not numbers where the digests are silent)

SourceScope hereTier
BauGB §§ 1, 12, 12a, 13a, 30, 34, 35Bauleitplanung; Zulässigkeit (FNP→B-Plan→§34/35) — framework; procedure NOT in the digested sources, VERIFYT1 law
BauNVO §16 Bauweise, §17 GRZ, §19 GFZ/OWZ, area types WA/WR/M/Sthe measure-of-use machinery — every numeric range in this file is a remembered placeholder, VERIFY per B-PlanT1 instrument
MBO §6 Abstandsflächen / state LBOs (e.g. §6 family; 3 m/0.4H)setbacksT2, state-amended, VERIFY
MBO Rettungswege/Treppen/Rauchmelder §§egress/stair/fire minimaT2, state versions, VERIFY
Stellplatz-/Abstandsflächensatzungen, Entwässerungssatzung, Hochwasserschutzkartensite duties, retention, hazardsT1 municipal, VERIFY
GEG + DIN 4108-2/-6, DIN V 18599energy + sommerlicher Wärmeschutz (S-index, F_C — in the digested physics source: kept bands quoted there)T2
DIN 4109 / VDI 4100; TA LärmSchallschutz; immission guide values (digest has the TA-Lärm table + DIN 4109-1 minimums)T2
DIN 18040-2; DIN 1946-2; DIN 1986-100barrier-free (claimed-only); Lüftungskonzept / drainage gradientsT2, VERIFY editions
DIN EN 1998-1/NAseismic zones (mostly 0; Oberrheingraben/Alpine fringe)T2, VERIFY
conception digest (structural rules)spans 5–7 m, one-way/30, 62.5 cm stud grid, ring-beam anchors, lintel spansT2-rules-of-thumb, VERIFY
Neufert Architects' Data / market normsfurniture clearances, room-size bands (3.2–3.3); body-dimension/movement-envelope tables, 2002 English edition, pp. 16–17 (3.9)T4
WoFlV; generic international habitable minimums (7.5/9.5 m²)WFL bands; sanity floor ONLYT1 / T3

Appendix B — Rules of thumb (metric)

ParameterValue
GRZ / GFZ / VGS / Wandhöhe / BaufensterB-Plan of THIS parcel — the ranges here are placeholders, VERIFY
Abstandsfläche familymax(3.0 m, 0.4·H) — state law, VERIFY
GFZ↔floors quick checkfloors ≈ GFZ ÷ GRZ_eff (2.2)
NTG target EFH72–80 %
Circulation8–14 %; > 18 % = misplaced stair
Flur / Diele≥ 1000 / entry 1400 · door clear ~860 (885/985 leaves)
Bedroom market floor12 m² (T3 absolute 7.5 — never sell that)
Eltern SZ · Kinder · Wohn-Ess-Koch · HWR · GWC15–18 · 12–15 · 45–60 · 7–9 · 3
F2F default2900 mm (2700 + 200)
Stair17 R @ ~170 / A ~280 (2S+A≈620); dog-leg well ~2.0×3.4 m
South canopyD ≈ H/tan(h_s); DACH 2.1 m window → ~1.0–1.2 m (6.1/7.3)
Court winter sun to floorW/H = 1/tan(90−φ−23.5°) ≈ 3.0–4.4 (DACH) — garden-scale
Lichtschacht min1.2×1.2; rough window opening ≥ 1/8 floor (S.1), openable ≥ 1/10 floor (sliders halve)
Cross-ventoutlet:inlet ≥ 1.25:1, low-in/high-out; night purge = summer strategy
Car bay / drive2.5×5.0 / 3.0 — GRZ-counted!
RC span economics≤ ~6–8 m one-way (conception)
Wet stackDN 100, ~1:50–1:100 (VERIFY DIN 1986), stacked baths
Brief-fitΣ T4 rooms ÷ (GFZ·A·NTG) ≤ 0.95 (3.8)
EVERYTHING in Sections 1–2 numbersT1-V — replace with the parcel's B-Plan before the model leaves study status

Appendix C — Client / authority intake (ask before Section 0.5)

Parcel & law: 1 B-Plan exists? §34 otherwise? → get the text plan + Plan-zeichenteil; 2 which GRZ/GFZ/VGS/Wandhöhe/Baufenster/Bauweise — transcribe with § numbers (never from memory, never from this file); 3 number of permitted Wohneinheiten; 4 Stellplatzsatzung + GRZ-anrechnung of garages/paths; 5 Entwässerungssatzung (retention?); Hochwasser/Gefahrenkarte; 6 state LBO (which Bundesland — Abstandsflächen + Melder +(height) versions differ); 7 Amtlicher Lageplan / Liegenschaftskataster extract (area, boundaries, easements Leitungs-/Wegerechte!); 8 Altlasten/Belastung, Kampfmittel? 9 Erschließung already paid/beitragsrechtlich secured (the German "no permit without Erschließung" gate).

Brief: 10 household now + in 10 years (Arbeitszimmer? Kinder? Alterssitz?); 11 units / Vermietung (decides stair + two entries, 5.4(6)/8.4); 12 rooms: HWR, Ankleide, Gäste-WC, workshop, Gartenraum; 13 sleeping-side sensitivity (street/Misch); 14 barrier-reduction ambitions (Dusch-WC, Aufzugsschacht reserve — accessibility-universal-design); 15 KfW/Energie-Standard (affects envelope massing + roof zone; route physics); 16 PV + Wallbox + Wärmepumpe positions.

Context: 17 city → φ (sun math 6.1) + climate region (DIN 4108-2 A/B/C — digest); 18 neighbours' windows/noise on all four boundaries (7.6 — go look, measure); 19 slope (8.6/2.6); 20 budget band (Keller yes/no, DHH vs freistehend trade-off). Then start Section 0.5 Step 1.


Appendix S: Source Check 2026-10 — values re-read from the literature

Each line below was read again in the source books (sources/) in October 2026, with the place it stands at. "Confirmed" means: a dated book prints the rule and names the standard or law; it does not mean the current edition of that standard was opened. State law (LBO) and local rules still override; VERIFY tags elsewhere in this skill stay in force unless a line here names the edition. Where a line here differs from a section of this skill, that section was corrected and names the line ("S.n"); the appendix governs.

S.1 Habitable rooms in the model building code (MBO)

  • Confirmed: a habitable room needs a clear height of at least 2.40 m (MBO); building

classes 1 and 2 and attics may deviate (most state codes: 2.30 m, attics 2.20 m). — Formeln und Tabellen Bauphysik 2.7.4 (p. 150); Gebäudetechnik 2.1.1.

  • Confirmed: the rough opening of the windows of a habitable room is at least 1/8 of the

net floor area of the room (MBO § 47); some states accept 1/10. — Bausanierung 14.4.2; Kompendium Nachhaltige Bauwerke 12.7.2; Gebäudetechnik 2.1.1. The "1/10 openable" of §3.1 and §4.3 is the weaker practice rule; where the two differ, 1/8 of the rough opening governs.

  • Confirmed (BayBO Art. 45 (1), version in force from 2026-05-01): habitable rooms need a

clear height of at least 2.40 m, in the attic 2.20 m over half of their floor, "wobei Raumteile mit einer lichten Höhe unter 1,50 m außer Betracht bleiben"; the sentence does not hold for habitable rooms in residential buildings of building classes 1 and 2. — sources/text/baybo/part-007.md.

  • Confirmed (BayBO Art. 35 (4), version in force from 2026-05-01): a window that serves as

a way out is at least 0.60 m wide and 1 m high, opens from inside and lies no higher than 1.20 m above the floor; in a roof slope or a dormer its lower edge, or a landing in front of it, is no more than 1 m from the eaves edge, measured horizontally. — sources/text/baybo/part-005.md.

  • Confirmed (BayBO Art. 45 (2), version in force from 2026-05-01): the rough opening of

the windows is at least 1/8 of the net floor area of the room "einschließlich der Netto-Grundfläche verglaster Vorbauten und Loggien": the floor of a glazed porch or loggia in front of the window is added to the room's. — sources/text/baybo/part-007.md.

S.2 Distance to the boundary (MBO 2019 § 6)

  • Confirmed: the depth of the setback area is 0.4 H, at least 3 m (0.2 H, at least 3 m in

commercial and industrial areas). — Bauphysik 4.2. State codes deviate; VERIFY per state.

  • Confirmed (BayBO Art. 6 (6) Nr. 2, version in force from 2026-05-01): balconies and

one-storey oriels are left out of the setback depth when together they take at most a third of the width of the outer wall, at most 5 m each, project at most 1.50 m from the wall and stay at least 2 m from the opposite boundary. — sources/text/baybo/part-002.md. A loggia inside the outline is no projection: the wall behind its open side is measured.

S.3 Defaults of this library for a simple house model

Not from a book. These are choices of this library, made so that a simple house can be modelled at all where the literature gives a frame and no number. Tier T4, massing only: any plan clause, product sheet, engineer's or carpenter's figure replaces them, and nothing here is a design value.

  • Least width of a living room: 3.5 m. §3.1 and §3.3 give widths for bedroom, bath and hall

only.

  • Finished ground floor 5 cm above the highest ground at the house: the entrance stays

step-free and the ground can fall away from the building. The plinth and the door threshold then need their waterproofing detail (roofing-waterproofing).

  • Base slab drawn 250 mm thick: the "slab 250" of the default set in §9.3.
  • Basement storey drawn 2.60 m from floor to floor: with the 200 mm floor slab above it

the rooms are 2.40 m clear, the least height of a habitable room (S.1), and the wall stays inside the 2.60 m clear height of a masonry basement wall without calculation (masonry-construction §9.5).

  • Outer wall of a basement drawn as 240 mm reinforced concrete with 120 mm perimeter

insulation outside: while ground and ground water are not known the model draws the safe side, the least cast-in-place wall of a watertight concrete structure under pressing water at w/z ≤ 0.55 (concrete-detailing §9.2, row "BKL-1 (0,55 line)"; the same figures in geotechnics-foundations §10.3), with the perimeter insulation of the worked cellar wall in construction-detailing §7.1. The ground report decides the real wall: masonry may do on dry, draining ground (masonry-construction §9.5), practice asks for 300 mm and more under a real head of water (concrete-detailing §9.2), and the earth pressure on the wall is the engineer's in every case (geotechnics-foundations §8.3).

  • Base slab under a basement drawn 250 mm thick, as a raft without strip footings: slab and

walls form one tank (geotechnics-foundations §6.4), and 250 mm is the slab of the same pressing-water row (concrete-detailing §9.2). The same number as the "slab 250" above, for another reason; the two may part.

  • Knee wall of an attic storey: drawn between 0.30 m and 1.80 m high, from the attic floor to

where the underside of the roof meets the outer face of the eaves wall. Above 1.80 m a local design statute no longer counts the wall as a knee wall (S.4); below 0.30 m the slope leaves no room at the wall, and the roof is drawn on the storey height instead.

  • Under a roof with a knee wall the outer walls of the attic reach up to the underside of the

roof and the inner walls up to the storey height, all of them cut by the slope. The storey height is then the height of a flat ceiling in the middle of the attic (a collar-beam ceiling), which the model does not draw; a room open to the ridge takes a storey height up to the ridge.

  • Ceiling under the loft (collar-beam ceiling): drawn as a plate 0.20 m thick, the thickness

the model gives a floor slab, with its underside at the storey height, so that the rooms keep the clear height the storey height gives them and the inner walls end under it. It spans between the two slopes, which cut its edges, and between the gable walls. Its top stays at least 0.50 m below the underside of the roof at the ridge, room for the ridge purlin and for a loft one can get into. The books give no thickness of such a ceiling.

  • With that ceiling a roof window ends below its underside, since above it a window would

light the loft and not the room; no stair is drawn up to the loft (a folding stair is not drawn); over the terrace of a roof cut-out the ceiling is left open; a dormer stays as it is, and where its roof rises higher than the ceiling, the room under it ends at the ceiling.

  • Usable depth of a loggia or balcony: at least 1.50 m from the wall to the guard. A small

table with a chair pulled out from it fits across that depth (§3.3, Dining: 700 to pull a chair out); the books give no depth of their own. The same 1.50 m is what a balcony may project in Bavaria and still stay out of the setback depth (S.2).

S.4 Attic storey under a pitched roof

  • Typical (local law, one example; Oberstaufen, Ortsgestaltungssatzung 2018, § 5 (2) and

(3), sources/text/dachgauben/part-005.md): knee walls of buildings of two and more storeys no higher than 0.80 m from the raw attic floor to the top of the eaves purlin; "Wandhöhen unter der Dachschräge (Rohdecke bis OK-Fußpfette) mit mehr als 1,80 m gelten nicht mehr als Kniestock". Other towns set other numbers or none; the B-Plan rules first.

  • Typical (Neufert 2002 p. 181, roofing-waterproofing S.5): a roof window at the knee wall

has its lower edge 0.90–1.10 m above the floor.

  • Confirmed (BayBO Art. 32 (1) and (2), version in force from 2026-05-01): "Jedes nicht zu

ebener Erde liegende Geschoss und der benutzbare Dachraum eines Gebäudes müssen über mindestens eine Treppe zugänglich sein"; "In Gebäuden der Gebäudeklassen 1 und 2 sind einschiebbare Treppen und Leitern als Zugang zu einem Dachraum ohne Aufenthaltsraum zulässig." — sources/text/baybo/part-004.md.

  • Typical (Holzbausanierung beim Bauen im Bestand 5.4.4, sources/text/holzbausanierung-beim-bauen-im-bestand/part-012.md

lines 446-456): in a rafter roof "Lediglich zur Begrenzung der Durchbiegung der Sparren sind Abstützungen (d. h. z. B. Scheren, Kehlbalken) notwendig"; stiffened to a plate, the collar-beam level carries horizontal forces to the gable and inner walls (the "unverschiebliche Kehlbalkendach"). Sizing is the engineer's (timber-steel-design).