name: timber-building-renovation description: > Historical timber construction diagnosis and repair for Bauen im Bestand: identifying and dating traditional Zimmermannsverbindungen (Verblattung, Verzapfung, Versatz, Verkämmung, Aufklauung and their named variants), regional Fachwerk/Blockbau/Umgebindebau typologies with dating tables, historic roof (Sparrendach/Pfettendach) and floor construction systems; damage diagnosis (Schadensanalyse) for wood-destroying fungi (Echter Hausschwamm, Nassfäulepilze, Hausporling, Blättlinge) and insects (Hausbock, Nagekäfer) with moisture/temperature thresholds and exit-hole identification, mechanical and chemical/corrosion damage, non-destructive and semi-destructive diagnostic methods (Bohrwiderstand, Ultraschall, Endoskopie, Bohrkern, dendrochronology) with DIN citations; residual capacity and damage assessment (Schadensbewertung) including DIN 68800 Gebrauchsklassen/Dauerhaftigkeitsklassen, safety cutback distances, and the historic-timber-grading problem under DIN 4074/DIN EN 1995; and repair/Ertüchtigung technique catalogs for roof feet, ridge joints, purlins, Fachwerk (Fußschwelle, Ständerfuß, Ausrichtung, Altholz reuse), Blockbau and Umgebindebau construction, with a full worked EC5 verification example. Use whenever a task involves an existing timber roof, floor, half-timbered (Fachwerk), log (Blockbau) or Umgebinde building — diagnosing damage, dating a connection or construction type, or planning a substance-preserving repair — as opposed to sizing new timber members, which is timber-steel-design, or the general structural-assessment/Nachrechnung machinery, which is existing-structures-retrofit. metadata: version: "1.0.0"


Timber Building Renovation (Holzbausanierung im Bestand)

Distilled from Lißner/Rug, Holzbausanierung beim Bauen im Bestand (Springer VDI-Buch). Covers the parts of "Bauen im Bestand" that are specific to historical timber construction: recognizing what you are looking at, diagnosing why it failed, judging what is still load-bearing, and choosing a substance-preserving repair. It does not repeat general retrofit/Nachrechnung mechanics or EC5 member design — see §9.

Reality check

  • This skill supports triage and preliminary repair planning. A licensed

Tragwerksplaner with timber-structures experience must verify any load-bearing repair before execution, and a Sachverständiger für Holzschutz/Holzschäden should confirm fungal/insect diagnosis before chemical or destructive intervention is specified.

  • Species-, fungus- and connection-specific numbers below (moisture

thresholds, cutback distances, cross-section reductions) are from a single German-language reference and regional field studies cited in it. Treat them as planning-stage defaults, not substitutes for an on-site survey — confirm before committing to a repair scope or cost estimate.

  • On a Denkmalschutz object, every repair decision below is subordinate

to the Denkmalschutzbehörde's approval; "substance-preserving" framing throughout this skill reflects that priority, not just cost.

  • Historic connection load capacities are order-of-magnitude planning

aids. A real verification always re-derives forces from the actual geometry and current DIN EN 1995-1-1/NA rules (§7.2 shows the method).

Evidentiary tiers and the [VERIFY] convention

  1. Normative — a currently valid DIN/DIN EN clause, cited by number.

Treat as binding unless superseded; confirm current edition before use, since editions and National Annexes change.

  1. Standards-of-practice / literature-sourced — values, thresholds or

rules-of-thumb from the cited book and the field studies it summarizes (e.g. Becker/Tichelmann's 50,000-case survey, ZHD Fulda mapping method). Solid planning defaults; state the source when citing them to a client or authority.

  1. [VERIFY] — a claim not traceable to a current standard's text in

this skill's source; typically because it is empirical/regional or the underlying standard has since changed. Re-confirm before relying on it.

1. Terminology (Bestandsbau-Begriffe)

German usage distinguishes these terms precisely; using them loosely invites scope disputes in a Sanierung contract:

  • Instandhaltung — keeps a building at its Sollzustand; no intervention

in structure or external form.

  • Instandsetzung — restores fitness for use; repairs/partial

replacement of damaged components, substance and geometry largely preserved (HOAI §2 Ziffer 8).

  • Sanierung — umbrella term (used inconsistently in practice) for all

technical measures restoring a construction's or building's usability; starts with removing damage and its causes.

  • Ertüchtigung — measures that raise properties above the original

level (load capacity, durability, fire resistance, thermal/acoustic performance) — not just restoration.

  • Modernisierung — gives the building a new quality it never had, with

a durable increase in use value or durable heating/water saving (HOAI §2 Ziffer 6).

  • Restaurierung — repair of culturally significant fabric, preserving

existing substance (SIA 469).

  • Rekonstruktion — rebuilding to the original form/type from evidence

(images, written sources); can extend to full historical rebuild.

  • Bestandsschutz — a structure lawful when built need not be adapted

to current building-law rules, unless a substantial change requiring permission, or a change of use, is planned — see existing-structures-retrofit for the full grandfathering mechanics.

2. Historical construction typology

2.1 Roof systems

Two structurally distinct families developed separately in the German regions before merging elements later:

  • Sparrendach (rafter roof) — rafters and ceiling joist form a rigid

triangle; loads go to the outer walls. Developed mainly in the Mittel-/Niederdeutsch region. A stehender Stuhl (standing queen/king post frame, used from ~1400) or liegender Stuhl (raking frame, frees usable roof space) provides longitudinal bracing and, on wide spans, intermediate rafter support via Kehlbalken (collar ties, introduced ~1200–1500) or a Firststütze (ridge post, from the 13th c.).

  • Pfettendach (purlin roof) — rafters are simply-supported beams on

purlins parallel to the ridge, spaced every 4–5 m; purlins need a Stuhl (queen-post frame) to carry their load down. Developed mainly in Süddeutschland (Donau/Alpine region); more adaptable to irregular plans, easier to calculate, common from the late 19th/early 20th c. onward. Subdivided into strebenlos (roof pitch < 30–35°, loads go straight to ceiling joists/walls) and abgestrebt (> 30°, loads diverted to outer walls via struts/Häng-/Sprengwerk).

Historical timeline of typical construction (chapter 3, Tab. 3.1 — use to date an unknown roof and anticipate what you will find):

PeriodTypical construction
Before 1870Sparrendach (≤~7 m span, pitch ≥35°, rafter length ≤4.5 m); Kehlbalkendach (rafter length 4.5–8 m, span ≤12 m); multi-stool Kehlbalkendach for wider/heavier cases; Hängewerk (1- or multi-fold); Mansarddach with 2–3-fold stool
1870–1918Pfettendach with 1- or multi-fold standing stool (≥1 stool at ridge, mandatory for saddle roofs on purlin framing); Drempelpfettendach; Pultdach with hanging or raking stool(s)
1918–1945Pfettendach (standing stool, with/without Drempel); simple Sparrendach/Kehlbalkendach persist
After 1945Simplified: Pfettendach (1–2-fold standing stool); Sparrendach/Kehlbalkendach, including Gittersparrendach (lattice rafter)

Kehlbalkendächer use ~20–30% less timber than Sparrendächer without collar ties — the driving reason they spread after WWI timber shortages. Historic sizing before ~1920 used carpenter's rules-of-thumb (Faustformeln, [VERIFY] regional variation), e.g. Sparrenhöhe H = L + 4 cm (1904, L = clear rafter length in m) vs. H = 5 cm + 2·L (1920/1939) — a useful sanity check when an as-built member looks under-sized by modern standards but has stood for a century.

Bohlendächer (plank-arch roofs, de l'Orme 1561, spread in Prussia via David Gilly from ~1797) economize timber by building arched binders from short curved planks (1.2–2.0 m long, ≥200–300 mm wide) nailed in 2–3 layers with staggered joints — occasionally still found over halls, riding arenas, churches; span/ply-count data in the source, [VERIFY] before reusing as a repair reference since national annex rules for built-up sections now apply.

2.2 Floor systems

Timber floor construction (Holzbalkendecken) followed the same regional split — joist bearing/anchoring to masonry (Balkenschuh, Mauerlatte, anchor irons through 3 joists) is the most common Bestandsaufnahme finding and the most common damage location (balcony/joist-end decay, §4.3.3.2). [VERIFY] joist spacing/species by direct survey — pre-1945 practice was regionally faustformel-driven like roof sizing above.

2.3 Fachwerk, Blockbau, Umgebindebau

Three load-bearing wall systems, each with distinct regional dating signatures (chapter 7.4 gives period-tagged construction catalogs per region — use these to date an unknown building from its frame geometry before opening anything):

  • Niedersächsisches Fachwerk (ländlich) — Mecklenburg farmhouse forms

dated by gable/roof form; Strohlehm-auf-Stakung infill typical before ~1850.

  • Niedersächsisches Fachwerk (städtisch) and **Mitteldeutsch-fränkisches

Fachwerk** — separate regional catalogs, each with its own bracing grammar (Streben, Kopfbänder, Fußbänder) and dating range.

  • Blockbau (log construction) — corner joints (Eckverkämmung) carry

the wall; U-value already ≈0.5 W/(m²·K) at 200 mm wall thickness from the timber alone if joints are wind-tight — usually no added insulation needed; fire resistance F30 achieved at 100 mm (single storey) or 180 mm (two storeys) [VERIFY current DIN EN 1995-1-2 edition].

  • Umgebindebau — hybrid: a free-standing internal timber frame

(Säulen, Rähm, Kopfbänder/Knaggen) carries the roof independent of the masonry or log outer wall, which is only a weather envelope. Regional Silesian/Lusatian form; single- and one-and-a-half-storey (with Drempel) variants dated to before/after 1550–1850 in the source catalog.

3. Historical connections catalog (Holzverbindungen)

3.1 Five basic types

Every traditional Zimmermannsverbindung is one of five basic types or a combination — recognizing which one you have tells you its likely load path, failure mode and repair options:

  1. Verblattung (halving/lap joint) — the oldest, originally

wedge-secured, later peg-secured (Holznagel). Load transfer only by contact bearing and friction — no meaningful tension capacity.

  1. Verzapfung (mortise-and-tenon)
  2. Versatz (notch/step joint, e.g. strut-to-tie) — transmits

compression through Vorholz bearing (see §7.2 for the modern EC5 verification of this joint type).

  1. Verkämmung (notch/cog joint) — e.g. joist bearing on a wall plate.
  2. Aufklauung (birdsmouth/notch seat) — rafter seating on a purlin.

Metallic fasteners (nails, Stabdübel, Dübel besonderer Bauart, adhesives) entered from ~1900 as spans and loads grew, driven by cheaper iron/steel — see §3.4 for the code timeline. Most Zimmermannsverbindungen were displaced by engineered fasteners in new construction over the 20th century, but survive throughout the existing stock and must still be assessed and often re-executed during repair — DIN EN 1995-1-1/NA:2013 retains design rules for them for exactly this reason.

3.2 Verlängerungsverbindungen (splices, along the grain)

ConnectionTypical useNotes
Gerader/schräger StoßSchwelle, Rähm, PfetteNeeds support at the joint; secured by steel straps, nails, cramps — usually inadequate alone
ZapfenstoßSchwelle, RähmGood, easily secured; historic tenon length up to 40 cm
SchwalbenschwanzstoßSchwelle, Rähm, MauerlatteAttested from the 1st c. AD
Gerader Stoß mit Haken(+Keil)/SchlossSchwelle, StielRepair-specific solution when a timber is too short for a lap
Gerades/schräges/HakenblattSchwellen, Rähm, PfetteSchräges Blatt reduces splitting vs. gerades Blatt; still the most common modern repair splice
Zahnverbindung (toothed splice)Balken, Stützen, Streben, 14th–19th c.Teeth 8/10–15/10 of member height, tooth depth 1/9 of height (for beams) or teeth 1.5–3.0× height with 1/10–1/8 depth (for columns/struts)

3.3 Cross, corner and angled connections

  • Querverbindungen (perpendicular members): Blatt variants (gerades,

schräges, Hakenblatt), Schwalbenschwanz (dovetail, from 1st c. AD), Zapfen variants (einfach, Doppel-, Brust-, geächselt, Kreuzzapfen), Verkämmung variants (einfach, Doppel-, Schwalbenschwanz-, Kreuzkamm, Schwabenkamm mit Dollen Ø20–30 mm).

  • Eckverbindungen (corners): stumpfer Eckstoß (weak, avoid relying on

it structurally), gerades/schräges Eckblatt, Scherblatt, Eck-/ Winkelzapfen (strongly weakens Schwelle/Rähm cross-section — check residual section at these points first when assessing an old frame).

  • Schrägverbindungen (raking members — struts, braces): glatter

Zapfen abgestirnt (standard for rafter/beam and Fachwerk strut connections), Jagdzapfen (good two-sided repair joint for head/foot braces), Versatz variants (einfach, doppelt, mit Zapfen).

  • Verstärkungsverbindungen: dübelverbundene Balken (side-driven dowels
  • bolt), armored beam splices with Schwerter (side plank splints) +

bolts — common repair pattern for cracked beams/rafters.

Roof- and floor-construction-specific application frequency tables (preferred/common/limited, by region and period) are in the source's §7.2–7.3 reference tables — consult before assuming a connection type is "wrong" for a given building's age and region.

3.4 Historic code timeline (for dating and assessing connections)

Knowing which code governed a connection when it was built explains why its detailing or allowable stresses differ from current EC5 — critical context before deciding a historic connection is "deficient":

YearCodeKey content
1920DIN 104 Bl.1First tables for Kleinhaus timber joists
1926DRB provisional rulesRaised allowable tension/compression parallel to grain; ω-method for buckling; bolted-connection rules
1928DIN 1990Building physics, wood protection, 80-year minimum design life
1933DIN 1052 (1st ed.)First DIN 1052; nail sizing rules (shank 1/6–1/8 of timber thickness in bending)
1938DIN 1052 (2nd ed.)Built-up compression members; uniform deflection limit L/300
1939DIN 4074 (1st ed.)First visual grading standard (Kantholz only)
1940DIN 1052 (3rd ed.)Grade-differentiated allowable stresses; L/200 deflection for purlins/rafters; Dübel needed police approval

Dübel besonderer Bauart (special dowel-type connectors) normed separately from 1925: rectangular dowels (1925 R.B.D. Stuttgart rules) → 1933 rectangular/disc/plate/ring/claw dowels permitted, cast-iron min. 5 mm wall thickness, bearing stress 8 N/mm² (a/t≥5) or 4 N/mm² (a/t<5) → DIN 1052 Bl.2:1969 names proprietary systems still found in the field (Ringkeildübel, Appel-Rippendübel, Beier-Ringdübel, Kübler-Dübel, Tuscherer-Dübel, Geka-, Bulldog-, Alligator-Dübel) → DDR TGL 33135/02:1984 → DIN 1052-2:1988 Typ A–E. Several of these proprietary types are still recognized in DIN 1052:2008 — useful when an as-built connector doesn't match any current catalog part.

4. Damage analysis (Schadensanalyse)

4.1 Damage statistics and classification

A nationwide survey of >50,000 damage cases (Becker/Tichelmann, 1991/92) groups timber damage into four causal classes; groups I (biological) and IV (moisture ingress) dominate and are causally linked — most biological damage traces back to a moisture-ingress cause. Damage frequency in the former East German states ran ~10 percentage points higher than in the West, and differed in character: Western-state damage is mostly attributable to renovation errors or improper use; Eastern-state damage to neglected maintenance of the fabric itself. One-third of mechanical- damage cases trace to load redistribution after a biologically-degraded member lost capacity — reinforcing why biological and mechanical assessment must be done together, not sequentially.

4.2 Wood-destroying fungi

All cause Braunfäule (brown/destruction rot) unless noted: wood longitudinal/transverse cracking, browning, residual substance crumbles to powder (cubical breakdown).

FungusSpeciesMoisture needTemp. optimum (°C)Notes
Echter HausschwammSerpula lacrimansLow at onset only; then self-transports water via strand mycelium — can attack dry wood and grow through masonry/fill8–26, narrow rangeThe dangerous one: hides in floor voids/behind cladding, growth often unnoticed until fruiting bodies appear on masonry/skirting/stair treads far from the timber; BGB §633 "erheblicher Sachmangel"; notifiable to the Bauaufsichtsbehörde in most Länder (e.g. SächsBO) alongside Hausbock and termites
Brauner Keller-/WarzenschwammConiophora puteanaNeeds sustained high moisture; survives desiccated >5 years, resumes on rewetting—Attacks softwood; thin, pale-to-blackish surface mycelium
Weißer PorenschwammAntrodia vaillantiiAs above—Attacks softwood; white, frost-flower-pattern surface mycelium
HausporlingDonkioporia expansaWood moisture >35%—Attacks hard- and softwood; does not grow through masonry
Blättlinge (3 species)Gloeophyllum abietinum/sepiarium/trabeum35–60% wood moisture—Often no visible surface mycelium — causes hidden internal rot (Kernfäule/Innenfäule) that can precede sudden collapse of a loaded beam if undetected

Strength drops fast under active Echter-Hausschwamm attack — bending strength falls measurably within a few months of infection (source fig. 4.65, [VERIFY] exact curve by species).

4.3 Wood-destroying insects

Table 4.5 — optimal (parenthetical: full development range) conditions:

Species (DE / Latin)Attacked partPreferred woodMoisture %Temp °CExit hole
Gewöhnlicher/Gemeiner Nagekäfer, Anobium punctatumwhole cross-sectionsoft- and hardwood30 (10–>50)22–23 (12–25)round, 1–2 mm, numerous
Hausbock, Hylotrupes bajulussapwood onlymainly softwood30 (10–>50)28–30 (10–>35)oval, ~4×7 mm, wavy larval galleries
Brauner Splintholzkäfer, Lyctus brunneussapwoodhardwood15–16 (8–22)28 (15–32)—
Mulmbock, Ergates fabermostly sapwood, rarely heartwoodsoftwood50 (20–>50)30 (15–>35)—
Trotzkopf, Anobium pertinaxmainly sapwoodfungus-damaged soft-/hardwood>50 (25–>50)22–25 (10–30)round, 2–3 mm
Gescheckter/Bunter Nagekäfer, Xestobium rufovillosumsapwoodmainly oak, also other hard-/softwood>50 (25–>50)22–25 (10–30)round, 3–4 mm

Hausbock is the most widespread structural pest, found chiefly on roof carpentry near open dormers/hatches and upper-storey joists. Its exit-hole pattern lets you estimate cross-section loss directly from the damage picture with experience; Nagekäfer damage cannot be estimated visually — assume the member needs opening/testing. Do not assume Hausbock is inactive just because the timber is old: activity has been documented in timber >60 years old, so a "historic, therefore dormant" assumption is not safe without a live-infestation check (stethoscope for feeding sounds, fresh bore dust, endoscopy).

4.4 Mechanical damage

Static overload chiefly comes from load redistribution after another member's biological failure, section loss, inaccurate original load assumptions, unqualified interventions (members cut with hand/chain saws during loft conversions), or unaccounted use-loads (change of use, snow- sack/ice/water pooling, accumulated storage loads). Timber is proven over centuries for static loads; dynamic loads (vibration, impact, seismic, explosion) can still cause cracking, fatigue fracture, deformation and fastener failure — smooth-shank nails, Einlassdübel and nail plates are the most vulnerable fastener types under dynamic/impact loading.

4.5 Chemical damage and corrosion

  • Wood resists weak acids and dilute alkalis; corrosion is generally

negligible in the pH range 2–11. Softwoods resist chemical corrosion better than hardwoods; glulam better than solid timber.

  • Fire-/wood-preservative salt overdose (mazeration): repeated

high-concentration treatment with K/NH₄-salt or phosphate-based products produces a wooly, defibered surface layer. Critical total salt load: >20 g/kg wood substance [source lit. citation]. Mazerated layer depth typically ≤5 mm (zero residual strength); the next 3–6 mm is not yet defibered but has strongly reduced strength — when assessing capacity, reduce the cross-section by 10 mm on all sides as a planning default for salt-mazerated members; small sections (e.g. battens) often have no residual capacity left and must simply be replaced. Oak resists these salts less well than softwood. Where PCP (pentachlorophenol)-based preservatives are found, the PCP-Richtlinie governs health assessment and remediation — treat this as a hazardous-materials trigger, not just a structural one.

  • Latten-/Sparren-Korrosion under tile roofing: sulfates leached from

tile clay, or calcium hydroxide leached from lime mortar bedding, cause a similar (but shallower, ~2–3 mm) surface mazeration on battens and rafters — easily mistaken for fungal mycelium; distinguish by testing, not appearance alone. Light cases: wire-brush off the salts; battens with reduced section and wide rafter spacing: re-batten.

  • Stress corrosion cracking of steel fasteners: nitrate-ion media

(ammonium sulfate, calcium ammonium nitrate, urea — common in agricultural storage buildings) cause invisible grain-boundary damage in loaded steel fasteners leading to sudden failure with no warning; risk increases with stress level, humidity, temperature and vibration. Only detectable metallographically in a lab. Two documented cases make the point: turnbuckle bolts from a Fachwerk frame hall after 50 years storing Kalkammonsalpeter showed 10–50% surface corrosion loss and grain-boundary damage to 0.6 mm depth even where surface corrosion was comparatively light; a separate bolt exposed to the same medium for only 10 years already showed grain-boundary damage to 0.8 mm depth — worse than the 50-year case despite far less exposure time. Treat any steel connector in a former agricultural/fertilizer/ chemical-storage building as a stress-corrosion suspect regardless of surface appearance or exposure duration, and sample metallographically before relying on it.

  • Corrosion protection of steel connectors: DIN EN 1995-1-1:2010 §4.2

(minimum protection by exposure class) for low corrosivity; DIN SPEC 1052-100:2013 Tab. 1 for moderate/severe/very severe. Tannin-rich species (oak, Bongossi) and preservative-impregnated timber both demand stainless or equivalently resistant fasteners (DIN EN 1995-1-1/NA:2013 NCI zu 4.2 (NA.6)).

4.6 Damage mapping (Schadenserfassung/-kartierung)

Document on as-built plans before any intervention, both to plan the repair scope and to support fee/cost estimation. The ZHD Fulda (Zentrum für Handwerk und Denkmalpflege) system is the standard methodology: graphic mapping by symbol/color for damage type, extent and depth, combined with a measurement/sampling log. Feed the result into Instandsetzungsdringlichkeit triage (which elements need action now vs. can be monitored) and an overall Zustandsklasse for the structure — parallels the Zustandsnote system in existing-structures-retrofit but at component rather than whole-structure granularity.

5. Diagnostic techniques (Untersuchungsverfahren)

Select method by: investigation goal, likely damage type, accessibility (occupied building? hidden members?), tolerance for destructive/semi- destructive testing, and required accuracy. None of these substitute for an experienced assessor's judgment — they are inputs to it.

ParameterMethodDIN / notes
Overall condition, hidden membersVisual (handnah), Abklopfen, Bebeilen, Eindringwiderstand (Stechbeitel)Non-destructive to destructive; first pass always
Pest IDEndoskopie (bore Ø5–20 mm), Fraßbild/exit-hole geometry, Stethoskop for live feeding sound—
Geometry/deformationMessband, Nivellier, 3D-Laserscan, Fotogrammetrie—
Moisture (wood)Electrical resistance (surface only — real distribution across the section can be very uneven)DIN EN 13183-2, accuracy ±0.5–1% (u<30%) / ±3–4% (u>30%)
Moisture (wood), reference methodGravimetric (Darr)DIN EN 13183-1, accuracy 0.1% of sample mass — used to calibrate field readings
Moisture (wood), capacitive—DIN EN 13183-3
Strength/density/moisture (direct)BohrkernentnahmeØ≥4 mm visual only; Ø15–25 mm for compression strength/density/moisture (practical field standard); Ø≥25 mm dendrochronology; Ø35–50 mm Dynstat (DIN 53435/TGL 1-204 Bl.8) or glulam glue-line shear (DIN EN 14080)
Compression strength (core vs. standard specimen ratio σ_core/σ_std)—Oak 1.18, spruce 1.09, pine 1.33 (mean); scatter 8% oak, 15% beech, 17.4% spruce, 10% pine
Dynamic E-modulus, defect locationUltraschall (longitudinal for grading; transverse for crack/glue-fault location, usable up to 1 m glulam thickness on a sound, low-crack surface)—
Internal condition profile, semi-destructiveBohrwiderstandsmessung (1.5 mm drill tip, constant feed/speed)Good for locating weak zones and active-fungus boundaries
Wood species/ageVisual/microscopy; Dendrochronologie (core Ø≥25 mm); RadiokarbonmethodeLab-grade dating options
CoatingsHaftprüfung, thickness/buildupDIN EN 24624/DIN 53151, DIN 50950/DIN 50986
Active fungusVitalitätstest, pH (oxalic acid), DNA analysis, chromatography—
Preservative content/contaminationExtractionDIN 52161-1/-7, DIN EN 351-2, DIN EN 212
Strength (destructive)Druckfestigkeit, Biegefestigkeit, Scherfestigkeit, ZugfestigkeitDIN EN 408 and DIN 52185/52186/52187/52188

Bore holes from core sampling can be plugged with matched new-wood plugs afterward — routine, not a reason to avoid coring where needed.

6. Damage/residual-capacity assessment (Schadensbewertung)

6.1 DIN 68800 Gebrauchsklassen and species durability

DIN 68800-1 (fully revised 2011/2012) replaced the older Gefährdungsklassen with Gebrauchsklassen (GK), assigned by exposure and documented per component:

  • GK 0 — permanently dry, indoors.
  • GK 1 — permanently dry.
  • GK 2 — under roof, not weather-exposed, but can exceed 18–20% moisture

for up to 6 months.

  • GK 3.1 / 3.2 — additionally weather/condensation exposed

(occasionally / frequently wet).

  • GK 4 — ground/earth contact; Moderfäule risk in addition to

Braunfäule, needs specific agents (e.g. copper salts).

Native species can be used without chemical wood preservative up to GK 3.2 if the right species/durability class is chosen (DIN 68800-1 §6.8.2.2, Tab. 5): spruce/fir/beech → GK 0 (heartwood not durable enough beyond that); pine heartwood → GK 0–2; larch/Douglas fir heartwood → GK 0–3.1; oak heartwood → GK 0–3.2. For GK 4 with native species, only Robinie qualifies (durability class 1–2) — but it has no DIN EN 1912 strength-class assignment, so use needs a case-by-case Zustimmung. Oak heartwood (durability class 2 per DIN EN 350-2) resists fungi well but is still attacked by Nagekäfer; beech is durable in strength terms but has essentially no natural fungal resistance untreated.

6.2 Safety cutback distances (bekämpfender Holzschutz)

When removing fungus-damaged wood under DIN 68800-4, cut back beyond the visible infection because hidden strength loss can extend further than visible damage:

  • Echter Hausschwamm: 1.0 m beyond visible attack (standard); can be

reduced to 0.5 m only where microscopy confirms the wood at that distance is uninfected — typically needed only where the full 1.0 m would compromise an otherwise-sound structural member.

  • Nassfäulepilze (Coniophora, Antrodia etc.): 0.3 m beyond visible

attack.

  • Fill/plaster near a Hausschwamm outbreak (Schüttstoffe, Putz):

remove 1.5 m beyond the infection boundary — the fungus can travel through masonry and fill invisibly, so treating only the timber invites reinfection of an already-"repaired" area. This failure mode (reinfection because the myzel in masonry/fill was ignored) is common enough to flag explicitly in every Hausschwamm repair scope.

  • On protected/decorated elements that cannot be removed (painted

beams, stucco ceilings, panelling), no method guarantees complete kill — document the residual reinfection risk in writing to the client.

6.3 The historic-timber-grading problem

DIN EN 1995-1-1/NA:2013 NCI Zu 1.1.2 (NA.5) explicitly extends the current design standard "sinngemäß" (by analogy) to Bauten im Bestand. But applying DIN 4074 visual grading to existing timber runs into practical obstacles worth naming explicitly before you rely on an as-built grade:

  1. Grading standards target sawn timber; pre-mid-19th-century members are

often hand-hewn.

  1. Grading is rarely actually performed in practice on existing timber —

engineers commonly default to S10 without checking whether a higher grade is achievable or a lower one is actually present.

  1. Visual grading legally requires trained personnel (DIN 4074-1/-2

§6.1) — a requirement essentially never met for in-situ grading of existing members.

  1. Members that aren't fully visible can't be checked against the full

criteria set (knots, grain angle, pith, ring width, cracks, wane, curvature).

  1. Machine grading requires certified equipment at an approved facility

— not deployable on built-in members.

  1. CE marking under DIN EN 14081-1 (a precondition for the sawn-timber

regulated-product status) is never present on historic members.

  1. Grading references 20% reference moisture (DIN 4074-1/-5 §3.3) —

existing dry timber often runs below that, [VERIFY] whether this yields an unexploited safety margin (not systematically studied per the source).

Practical path: density is comparatively easy to determine on built-in timber (bore cores, §5) and DIN EN 338 now tabulates characteristic and mean density per strength class — use density-based estimation as the practical route to a strength class assignment for existing members, combined with a careful visual pass, rather than either skipping grading or claiming full DIN 4074 compliance you cannot actually demonstrate. Historic glulam (pre-1968, e.g. Hetzer, Christoph & Unmack, Kübler production) cannot be assigned a current DIN EN 14080 class at all — needs case-specific testing every time. See timber-steel-design for the EC5 member verification once a strength class is established, and existing-structures-retrofit for the general reduced-γM Nachrechnung framework this feeds into.

6.4 Moisture content categories

  • darrtrocken (kiln-anhydrous): u = 0%
  • trocken (dry): u ≤ 20% (DIN 4074-1/-5 §3.3)
  • halbtrocken (semi-dry): 20% < u ≤ 30% (≤35% for sections >200 cm²)
  • fasergesättigt (fiber-saturated): u = 22–36%
  • nass/saftfrisch (wet/green): u ≥ 30% (≥35% for sections >200 cm²)

Konstruktionsvollholz (KVH) carries a guaranteed u = 15% ± 3%. New replacement timber should be pre-dried to the expected in-use equilibrium moisture before installation — documented case: a non-predried oak replacement sill took >3 years for its outer zone to reach in-use moisture, and the mortise/tenon interior stayed at 20–40% (fungus- favorable) throughout, because shrinkage gaps kept exposing the joint to extra moisture. Always specify pre-dried replacement timber in a Fachwerk/Blockbau repair scope for exactly this reason.

7. Repair and retrofit methods (Instandsetzung/Ertüchtigung)

7.1 Roof-foot (Dachfuß/Sparrenfuß) repair catalog

The roof foot (rafter/tie-beam bearing) is the single most common damage hotspot (moisture ingress from delayed maintenance) and therefore the most-repaired detail. Repair method depends on whether it is a Sparren-/ Kehlbalkendach (rafter carries bending + axial force) or Pfettendach (rafter carries bending only):

  • Minor section loss at a Versatz/Zapfen foot connection: Brettlaschen

(board splints, both sides), additional Simplex bolted connection, or a Knagge (corbel block) combined with a Stirn- or Fersenversatz.

  • Longer damaged rafter feet: two splint boards required (axial force

must be carried symmetrically), verbindungsmittel count set by the calculated force, grouped in two clusters spaced at roughly a fifth of the connection length; long-Blatt (lap) splicing is the traditional alternative, still common on historic roofs.

  • Local, non-end damage (Merk-Lamellen-Verfahren): step-cut back to

sound wood, glue in matched board lamellae — a material-honest partial repair rather than wholesale replacement, preferred where substance preservation matters.

  • Combined rafter+joist+purlin damage at the foot: full three-element

repair, combining the splint/splice/Merk-Lamellen methods above per element. existing-structures-retrofit §8.6 identifies embedded beam ends (Balkenköpfe) in damp masonry as the classic rot pocket at assessment level but explicitly defers the timber-specific repair technique to this skill — this is that technique.

7.2 Worked example: EC5 verification of a reinforced rafter foot

Demonstrates the general method — re-derive geometry from survey, verify per current DIN EN 1995-1-1 — that should be applied to any historic Versatz/Knagge repair, not just this specific case.

Given: strut force N₍S,d₎ = 23.75 kN at α = 47°; existing rafter and tie beam: old-growth softwood (pine), visually undamaged, field-sortable as S10 per DIN 4074-1; new corbel (Knagge): new softwood S10, dry- sorted, NKL 2, KLED short. Rafter/corbel width 160 mm, Aufklauung depth tₖ, Versatztiefe tᵥ = 40 mm, Anschlusslänge Lₐ = 340 mm.

  1. Required Aufklauung depth from bearing check

f_c,0,k = 21 N/mm² (S10 → C24 per DIN EN 1912/DIN EN 338 Tab.1); f_c,0,d = k_mod·f_c,0,k/γ_M = 0.9·21/1.3 = 14.54 N/mm²; erf. tₖ > N_S,d /(b·f_c,0,d) = 23.75·10³/(160·14.54) = 10.2 mm → chosen tₖ = 20 mm.

  1. Eccentricity and reaction forces: e = h_Knagge − tₖ/2 −

tᵥ/(2·cos α) = 160 − 10 − 29.3 = 120.7 mm; lever arm Lᵥ = ⅚·Lₐ = 283.3 mm; from moment equilibrium F_Z,d = F_D,d = N_S,d·e/L_V = 10.12 kN.

  1. Bearing under the washer (bolt M16, washer per DIN EN ISO 7094,

outer Ø56 mm): σ_c,90,d ≈ 4·F_Z,d/(π·(56²−17.5²)) = 4.55 N/mm²; f_c,90,d = k_mod·3.0·f_c,90,k/γ_M (contact-face factor 3.0 per DIN EN 1995-1-1:2010 §8.5.2(2)) = 0.9·3.0·2.5/1.3 = 5.19 N/mm²; utilization 4.55/(1.0·5.19) = 0.88 < 1.0 — OK.

  1. Fersenversatz (heel notch) check: effective shear length capped

at ℓ_v,eff = 8·t_v = 320 mm per DIN EN 1995-1-1/NA:2013 NCI NA.12.1 (NA.4); effective width b_ef = k_cr·b with k_cr = 2.0/f_v,k = 0.5 (f_v,k = 4.0 N/mm²) → b_ef = 80 mm; τ_v,d = 16.2·10³/(80·320) = 0.63 N/mm² against f_v,d = 0.9·4.0/1.3 = 2.77 N/mm² → utilization 0.23 < 1.0.

  1. Stirnfläche (end-grain bearing at angle α): σ_c,α,d = N_S,d/A_Stirn

= 23.75·10³/6400 = 3.71 N/mm²; f_c,α,d via Hankinson-type formula (DIN EN 1995-1-1/NA:2013 Gl. NA.163) = 5.50 N/mm² → utilization 3.71/5.50 = 0.67 < 1.0.

All checks pass with margin (0.23–0.88) — a repair geometry sized on constructional/carpentry judgment (round numbers: 20 mm claw depth, 40 mm notch depth) rather than tight optimization, typical of how these repairs are actually detailed on site. See timber-steel-design for the general EC5 connection design method this example specializes.

7.3 Ridge, collar-tie and purlin repair

  • Firstknoten (ridge joint, typically Scherzapfen or Blatt +

Holznagel on old Sparrendächer): repair by applied splints, or — denkmalgerecht — by scarfing in matched new wood, combined with longitudinal bracing to arrest lateral ridge-line deformation (a common secondary symptom of a failed ridge joint).

  • Kehlbalkenanschluss: corbel + securing screw, partial replacement

with splints, or an under-set board with nailed splints — all relatively simple once the connection is exposed.

  • Pfetten-/Rähmkonstruktion: historic purlin framing is often

deliberately under-stiff by modern standards (our forebears accepted some flexibility here) — modeling it as a rigid support in a Nachrechnung will flag a "deficiency" that reflects the model, not necessarily an unsafe structure; discuss with the Tragwerksplaner before automatically speccing reinforcement. Where reinforcement is genuinely needed: section enlargement (timber, wood-based panel, or steel plates) or a static-system change (continuous-beam action, Gelenkpfette, or added intermediate support to cut the span).

7.4 Fachwerk-specific repair

  • Frame members (Gefüge): local defects — trim/chase back

(Bebeilen/Einstemmen, min. 4 cm) and splice in matched, dry, same- species wood, accounting for differential shrink/swell. Larger damage, especially at nodes, needs a Tragwerksplaner's calculation and a matching temporary shoring design; if the residual section is insufficient, use the splice/reinforcement methods of §3.2/§7.1.

  • Fußschwelle (sill beam): damp sill is caused by a wet plinth in

nearly 100% of cases — fix the moisture source (horizontal + vertical damp-proofing in the plinth masonry) before or alongside any timber repair, or the repair will fail again. Partial replacement is possible where damage is localized; full replacement is installed from the side or from below depending on plinth condition, reusing sound tenons where possible; the new plinth must be set back or chamfered so water actually drains off it.

  • Ständerfußerneuerung (post-foot replacement): method matches

damage extent/type; on heavily loaded wall sections use concealed Stabdübel/Passbolzen instead of Holznägel at the joint for extra shear security.

  • Holznägel (timber pegs): primarily positional fixing, not

necessarily meant to carry load — but oak pegs meeting minimum spacing and diameter rules can be designed as a load-carrying connection (see §6.3 cross-reference to timber-steel-design). Square or round in section, from oak, pine, hornbeam, acacia, cherry or spruce; bore hole 1–3 mm undersized vs. the peg; peg size (side length or diameter) 16–40 mm depending on application. Members are traditionally bored "auf Zug" (holes slightly offset) so the peg draws the joint tight — understand this before assuming a loose-looking peg joint is defective.

  • Ausrichten (straightening the whole frame): not every lean needs

correcting — minor deformation and naturally crooked timber are Fachwerk-typical and preserving them keeps the facade's authentic appearance and avoids damaging sound infill panels (Gefache). Only straighten where standing stability is genuinely compromised (e.g. leaning on a neighboring building) and only after full gutting (Gefache removed). Use ropes/carpenter's winches, avoid inducing new stresses, fix by wedging tenon/lap joints and re-boring pegs; steel angle bracing as a last resort, concealed drawn steel pins where hidden.

  • Altholz-Wiederverwendung (reusing old timber): old and new timber

show no meaningful strength difference — reuse is structurally sound where the member is otherwise healthy. But decades-old deflection in a reused member cannot be "undone" by reinstalling it differently — long-compressed fibers crack quickly and won't regain capacity if re-loaded against their set; reinstall with the same deformation and matching load orientation it already carries. On full deconstruction: dismantle carefully, sort, clean (pressure water/steam works well), let dry fully before use, protect from rain/splash in storage, stack oriented by cross-section with ventilation gaps, discard any pest-infested pieces before restacking.

7.5 Blockbau (log construction) repair

  • Corner joints (Eckverkämmung) are rebuilt zimmermannsmäßig to the

historic pattern as a precision fit — this is a load-bearing detail, not decorative.

  • Replacing whole wall sections: account for shrinkage; new sill

bearing/height follows the same principles as Fachwerk (§7.4), kept above the splash-water zone.

  • Localized section loss: repair pieces ≥4 cm thick, oriented core-side

out to control deformation.

  • Wall U-value already ≈0.5 W/(m²·K) at 200 mm if inter-log joints are

wind-tight — added insulation is usually unnecessary; focus retrofit effort on the ground-floor/cellar interface and ceilings to unheated spaces instead (cross-ref building-physics-thermal-moisture).

  • Fire resistance: F30 at 100 mm wall thickness (single storey) or

180 mm (two storeys) [VERIFY current DIN EN 1995-1-2 edition and national annex before citing as compliance evidence].

  • Log-course joints: fill with natural materials to the historic

detail — Werg (tow), coconut fiber, cork, tarred hemp rope, or clay-chaff mixes — never with permanently-elastic sealants, which prevent the intended fiber compression at the joint under wall load.

7.6 Umgebindebau repair strategy

Organize the repair scope into the building's four structurally distinct subsystems, since they behave and fail independently:

  1. Blockstube (log room) including its foundation — repair per §7.5.
  2. Load-bearing Fachwerk portion — repair per §7.4.
  3. Masonry portion (Massivbau) — hand off to masonry-construction.
  4. The Umgebinde frame itself (columns, Rähm, Kopfbänder/Knaggen) — this

is the system that actually carries the roof independent of the masonry/log walls; treat its members with the roof/floor repair methods of §7.1–7.3, and verify it is not being inadvertently loaded by settlement or stiffening of the (non-structural) infill walls around it.

8. Reference: typische Schadbilder (damage-picture catalog)

Condensed from the source's 15-entry catalog — use as a rapid field checklist; each entry's "measures" column is a starting point, not a substitute for §4–§7:

#Damage pictureTypical causeFirst measures
1DurchfeuchtungRoof/drainage defect, rising damp, poor insulation/ventilationEliminate moisture source; assess fungal risk
2VerfärbungenMoisture, temperature, chemical attack, discoloring fungiDistinguish cosmetic vs. strength-affecting; assess
3BewachsungenFungi, moss, plants under moistureEliminate moisture; remove growth; check adjacent areas
4Strukturveränderung (Fäule)Wood-destroying fungi + elevated moistureSpecies ID, activity test, remove infected wood, assess residual capacity
5Fraßbilder (insects)Wood-destroying insects, sometimes fungus-preconditionedSpecies ID, activity test, treat, assess residual capacity
6Chemische KorrosionAggressive atmosphere/mediaAssess strength/stability impact; consider surface treatment
7Thermische Schädigung≥60°C sustained; ignition ~230°C; self-ignition 350–400°C; aggressive gasesAssess strength/stability impact
8RisseShrink/swell, heat/moisture, static/dynamic overload, differential settlementAssess cause, size, location before deciding on repair
9Fehlende BauteileOverload/total loss, or careless removal during past alterationsRestore original construction or substitute the lost function elsewhere
10Form-/LageveränderungUse loads, wind, uneven settlement, inadequate bracing, material defectsAssess stability/function impact
11QuerschnittsschwächungenConnections, material defects, biological/chemical attack, fire/explosionAssess per cause; frequently combines with #4–#6
12Gebrochene BauteileStatic/dynamic overload, often on a pre-weakened sectionReplace, or reinforce/relieve per cause
13AbnutzungUse-related wear, impact, weathering, agingReplace/reinforce below minimum required section
14Verbindungs-VeränderungenOverload, deformation, biological/chemical attackRestore load/function capacity of the connection
15Stahlteil-KorrosionMoisture, chemical attack, static loadAssess load/function impact; consider §4.5 stress-corrosion risk

9. Cross-references

  • `timber-steel-design` — EC5 member and connection design for any

new or replacement timber sized during a repair; this skill supplies the historic-material input (grade, residual section, connection geometry) that feeds that sizing.

  • `existing-structures-retrofit` — the general Bestand structural-

assessment framework: Bestandsschutz/Nachrechnung mechanics, γM reduction under qualified-inventory conditions, Zustandsnote system, joist-head repair technique this skill's rafter-foot method mirrors. Use it for the load-path/Nachrechnung machinery; use this skill for timber-specific diagnosis and repair technique.

  • `building-renovation-refurbishment` — non-structural/whole-building

renovation planning (survey workflow, GEG energetic retrofit, ecological materials, permits) that a timber-structure repair sits inside; that skill hands off to this one for anything touching an existing timber roof, floor or frame.

  • `structural-systems` — load-path/grid concept selection if a

repair also changes the structural concept (e.g. removing a load- bearing Fachwerk wall).

  • `construction-freecad-bim` — the renovation/retrofit modeling

workflow (status-tagged Bestand/Neu objects, degraded-material property override feeding run_fem_analysis) for building a repair into a BIM model; §6 residual-capacity values above are the direct input to that override.